Plan Review Notes
Plan Review Notes For Permit 05120685
Permit Number 05120685
Review Stop M
Sequence Number 2
Notes
Date Text
2006-02-15 00:00:00*** DENIED ***
 1) PLEASE ADD COMBUSTION AIR
 CALCULATIONS TO THE MECHANICAL PLANS FOR
 THE GAS CLOTHS DRYER, AND THE GAS WATER
 HEATER SHOWING THE BTU'S, CUBIC FEET,
 OPENING SIZE, ECT. PER 2004 FBC/R CH. 17
  
 2) NEED TO SUPPLY COMBUSTION AIR FOR GAS
 CLOTHS DRYER, AND GAS WATER HEATER, PER
 2004 FBC/R CH. 17.
  
 3) PLEASE PROVIDE THE PAGE WITH THE U.L.
 APPROVAL FOR THE GAS GRILL.
  
 4) THE INFORMATION YOU PROVIDED FOR THE
 HOOD IS FOR A RANGE NOT A GRILL (SEE
 ATTACHED SAMPLE).
  
 5) PLEASE PROVIDEDETAILED
 MANUFACTURE'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR THE
 VENTLESS FIRE PLACE IN THE LIVING ROOM,
 AND THE COVERED PATIO.
  
 6) PLEASE PROVIDE MANUAL J CALCULATIONS
 TO GO WITH YOUR ENERGY CALCULATIONS
 SUBMITED, PER 2004 FBC 13-607.1.ABC.1 .
  
 7) PLEASE BE INFORMED THAT WHEN
 SUPPLYING AIR CONDITIONING TO A GARAGE
 TO COMPLY WITH 2004 FBC/R 309.1.1 DUCT
 PENETRATIONS AND R 309.2 SEPARATION
 REQUIRED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  