| Plan Review Notes For Permit 05120685 |
| Permit Number |
05120685 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-02-15 00:00:00 | *** DENIED *** | | | 1) PLEASE ADD COMBUSTION AIR | | | CALCULATIONS TO THE MECHANICAL PLANS FOR | | | THE GAS CLOTHS DRYER, AND THE GAS WATER | | | HEATER SHOWING THE BTU'S, CUBIC FEET, | | | OPENING SIZE, ECT. PER 2004 FBC/R CH. 17 | | | | | | 2) NEED TO SUPPLY COMBUSTION AIR FOR GAS | | | CLOTHS DRYER, AND GAS WATER HEATER, PER | | | 2004 FBC/R CH. 17. | | | | | | 3) PLEASE PROVIDE THE PAGE WITH THE U.L. | | | APPROVAL FOR THE GAS GRILL. | | | | | | 4) THE INFORMATION YOU PROVIDED FOR THE | | | HOOD IS FOR A RANGE NOT A GRILL (SEE | | | ATTACHED SAMPLE). | | | | | | 5) PLEASE PROVIDEDETAILED | | | MANUFACTURE'S SPECIFICATION'S AND | | | INSTALLATION INSTRUCTIONS FOR THE | | | VENTLESS FIRE PLACE IN THE LIVING ROOM, | | | AND THE COVERED PATIO. | | | | | | 6) PLEASE PROVIDE MANUAL J CALCULATIONS | | | TO GO WITH YOUR ENERGY CALCULATIONS | | | SUBMITED, PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 7) PLEASE BE INFORMED THAT WHEN | | | SUPPLYING AIR CONDITIONING TO A GARAGE | | | TO COMPLY WITH 2004 FBC/R 309.1.1 DUCT | | | PENETRATIONS AND R 309.2 SEPARATION | | | REQUIRED. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|