| Plan Review Notes For Permit 05120685 |
| Permit Number |
05120685 |
|
| Review Stop |
E |
| Sequence Number |
10 |
|
| Notes |
| Date |
Text |
| 2007-02-02 13:29:54 | | | | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THE LOAD ON THE POOL PANEL EXCEEDS | | | THAT OF THE RATING OF THE BREAKER WHICH FEEDS THE POOL | | | PANEL. | | | PLEASE SEE PREVIOUS PANEL SCHEDULE AND THIS PANEL | | | SCHEDULE SHOWS 10.2 KW ON A 40A BREAKER. | | | | | | 2) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER CURRENT | | | PROTECTION FOR HEAT STRIPS/AHU?S AT 125%. | | | | | | 3) NOTE: PLEASE SEE POOL PUMP WHICH SHOWS A 1-POLE | | | BREAKER AND A LOAD OF 2300 VA. | | | PLEASE VERIFY LOAD AND/OR THE NUMBER OF POLES. | | | 230.42, 240.4, 310.16 ETC. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|