Date Text
2007-02-02 13:29:54 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE LOAD ON THE POOL PANEL EXCEEDS
 THAT OF THE RATING OF THE BREAKER WHICH FEEDS THE POOL
 PANEL.
 PLEASE SEE PREVIOUS PANEL SCHEDULE AND THIS PANEL
 SCHEDULE SHOWS 10.2 KW ON A 40A BREAKER.
  
 2) NOTE: PLEASE SEE 424.3B FOR THE MINIMUM OVER CURRENT
 PROTECTION FOR HEAT STRIPS/AHU?S AT 125%.
  
 3) NOTE: PLEASE SEE POOL PUMP WHICH SHOWS A 1-POLE
 BREAKER AND A LOAD OF 2300 VA.
 PLEASE VERIFY LOAD AND/OR THE NUMBER OF POLES.
 230.42, 240.4, 310.16 ETC.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  