Plan Review Notes
Plan Review Notes For Permit 05120685
Permit Number 05120685
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-29 00:00:00DENIED;
 1.PLANS REVIEW WITH FBC-2004 PLUMBING
 CODE, CHANGE NOTE.
 2.PERSON RESPONSIBLE FOR DRAWING IS
 REQUIRED TO SIGN DRAWINGS. 104.2.1
 3.AUTOMATIC CLOTHES WASHER SHALL CONNECT
 TO A BRANCH DRAIN OR STACK A MINIMUM OF
 3" IN DIAMETER.
 4.BOTH BIDETS IN MASTER BATHROOM ARE NOT
 VENTED.
 5.SIZE ALL PIPES 3" WET VENT REQUIRED
 AFTER SHOWER DRAIN IN MASTER BATHROOM.
 (5 FUS)
 6.BATH #3 BIDET NOT VENTED.
 7.BBQ SINK TO DISCHARGE DOWN STREAM OF
 THE CABANA BATH GROUP. SEE SEC. 909.1.
 8.INSTALL TRAP PRIMER IN LAUNDRY ROOM
 FLOOR DRAIN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695