Plan Review Notes
Plan Review Notes For Permit 05120640
Permit Number 05120640
Review Stop B
Sequence Number 2
Notes
Date Text
2006-02-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW:
  
 1.)THE ARCHITECT'S TITLE BLOCK IS TO
 INCLUDE ALL INFORMATION REQUIRED BY
 FAC61G1-16.003, 004.
  
 A TITLE BLOCK IS REQUIRED FOR EACH
 SHEET.PLEASE FAMILIARIZE YOURSELF WITH
 YOUR BOARD'S REQUIREMENTS.FAILURE TO
 SUBMIT PAPERWORK IN COMPLIANCE WITH
 FAC61G1-16 MAY RESULT IN A COMPLAINT
 AGAINST YOU.
  
 2.)ADDRESSED.
  
 3.)THE STATE PRODUCT APPROVAL FOR THE
 FRENCH DOOR (FD101) DOES NOT MATCH THE
 NOA SUBMITTED (FD750).IF STATE
 APPROVAL IS NOT AVAILABLE, PLEASE APPLY
 FOR LOCAL PRODUCT APPROVAL.FAC9B72.
  
 ADDRESSED; HOWEVER, THE PRODUCT APPROVAL
 ON THE STATE WEBSITE HAS CHANGED AS THE
 ONE YOU PROVIDED IS TWO YEARS OLD.
 PLEASE PRINT A NEW STATE APPROVAL.
  
 4.)MULLIONS ARE SHOWN ON THE PLAN.
 PROVIDE MULLION PRODUCT APPROVALS.
  
 THIS WAS ADDRESSED BY A DETAIL FROM THE
 ARCHITECT.MULLIONS ARE TO BE TESTED
 OR ENGINEERED, FBC1714.5.5.1.THE
 ARCHITECT SPECIFIED "3 2X4 MULLION".
 THIS APPEARS TO BE A FRAMING DETAIL
 RATHER THAN MULLION ENGINEERING.THIS
 IS ACCEPTABLE, BUT PLEASE CONFIRM THAT
 YOU WANT TO HAVE TRIPLE STRUCTURAL 2X4
 BETWEEN THE TWO WINDOWS RATHER THAN A
 METAL MULLION.PLEASE CONTACT ME IF YOU
 NEED ASSISTANCE IN UNDERSTANDING THIS
 CORRECTION.
  
 NEW COMMENT:
  
 5.)IF YOU ARE GOING TO USE THE
 STRUCTURAL 2X4S BETWEEN THE WINDOWS,
 HAVE THIS DETAIL REVIEWED BY HISTORIC
 PRESERVATION DEPARTMENT.
  