Plan Review Notes For Permit 05120638
Permit Number 05120638
Review Stop E
Sequence Number 4
Notes
Date Text
2006-07-21 00:00:00REDLINED **
  
 PLACEMENT OF SD'S PER NFPA-72
 11.5.1.1,11.8.3
 CONDUIT FROM METER TO PANEL IS TO BE IN
 SLAB OR MAIN MUST BE ADDED W/ OCP ON THE
 OUTSIDE. 230.6,230.70