| 2008-06-24 11:16:18 | PLUMBING PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | 1. ALL REVISIONS TO A SIGNED/SEALED SET OF PLANS SHALL |
| | BE SIGNED & SEALED BY THE ENGINEER OF RECORD. PER |
| | (W.P.B. AS AMENDED) SECTION 106.1. |
| | NOTE: THE ORIGINAL ENGINEER OF RECORD IS SENG-CHAI TAN |
| | PE LICENSE #46765, HOWEVER THE SUBMITTED PLUMBING |
| | REVISION IS SIGNED AND SEALED BY HENRY MELENDEZ, PE |
| | LICENSE #62946 WHO IS NOT THE ORIGINAL ENGINEER OF |
| | RECORD. PLEASE HAVE ORIGINAL ENGINEER OF RECORD SIGN, |
| | SEAL AND DATE REVISIONS. |
| | |
| | 2. THE FOLLOWING ITEMS NEED TO BE CORRECTED ON THE |
| | SANITARY PLUMBING RISER REVISION: |
| | |
| | A} ISOMETRIC DOES NOT REFLECT THE FLOOR PLAN. THE |
| | LAVATORIES ARE BEING SHOWN AS BEING IN THE WALL NOT IN |
| | THE BATHROOMS AND WHAT KIND OF FITTING IS BEING USED IN |
| | THE SHOWER BATH FOR THE WATER CLOSET. AT A MINIMUM THE |
| | ISOMETRIC SHALL REFLECT THE FLOOR PLAN. PER FBC- |
| | PLUMBING SECTION 701.1 SCOPE. |
| | |
| | B} A 3 INCH CLEANOUT IS REQUIRED FOR THE WASHING |
| | MACHINE WASTE STACK AND SHALL BE LOCATED AT FOUR FEET |
| | ABOVE FINNISH FLOOR (4' A.F.F.). PER FBC- PLUMBING |
| | SECTION 708.3.4 AND 708.9 ACCESS. |
| | |
| | C} A TWO-WAY CLEANOUT IS REQUIRED AT THE JUCTION OF |
| | THE BUILDING DRAIN AND BUILDING SEWER. PER FBC- |
| | PLUMBING SECTION 708.3.5. |
| | |
| | D} THE 2 INCH VENT THRU THE ROOF ARE BEING INDICATED |
| | AS UTR, THEY SHOULD BE INDICATED AS VTR. PER FBC- |
| | PLUMBING SECTION 901.1 SCOPE. |
| | |
| | E} CLEARLY IDENTIFY WHAT KIND OF VENT IS BEING USED |
| | FOR THE KITCHEN SINK VENT. IS IT AN AIR ADMITTANCE |
| | VALVE (A.A.V.) OR IS IT A VENT THRU THE ROOF (VTR)? IT |
| | APPEARS THAT A 42" HIGH KNEE WALL IS AT THIS LOCATION |
| | AND AN A.A.V. SHOULD BE USED. PER FBC- PLUMBING SECTION |
| | 901.1 SCOPE. |
| | |
| | F} CLEARLY IDENTIFY THE LAVATORY WASTE ARMS AS BEING |
| | 1-1/2". PER FBC- PLUMBING SECTION 701.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |