Plan Review Notes
Plan Review Notes For Permit 05120638
Permit Number 05120638
Review Stop E
Sequence Number 3
Notes
Date Text
2006-07-13 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT
 ALL CONDUCTORS IN A BUILDING OR OTHER
 STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.
 230.70(A)(1)-READILY ACCESSIBLE
 LOCATION. THE SERVICE DISCONNECTING
 MEANS SHALL BE INSTALLED AT A READILY
 ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST
 THE POINT OF ENTRANCE OF THE SERVICE
 CONDUCTORS.
  
 THE NOTE ABOUT "RUNNING OVERHEAD IN
 TRUSSES" ON THE RISER DICTATES THAT A
 MAIN DISCONNECT BE LOCATED OUTSIDE,
 PREFERABLY BY THE METER. PLEASE SHOW
 SAME ON RISER AND LOCATE THE MAIN ON THE
 PLAN. THIS IS THE SAME COMMENT THAT WAS
 MADE IN THE FIRST REVIEW.
 THERE WAS A DISCONNECT ADDED TO THE
 6,8,06 PLAN, BUT REMOVED FROM THE PLAN
 SUBMITTED 7/13/06.
  
 2} THE RECEPTACLE SPACING IN THE MASTER
 SUITE, GREAT ROOM, BEDROOM #3, AND THE
 KITCHEN DOES NOT COMPLY WITH
 210.52(A)(1), 210.52(A)(2), AND
 210.52(C)(1). THESE RECEPTACLES WERE ON
 THE THE PLANS DATED JUNE 8, 2006, BUT
 HAVE BEEN REMOVED FROM THE PLANS
 SUBMITTED ON 7/13/06, DATED JULY 7TH,
 2006 BY THE STRUCTURAL ENGINEER. PLEASE
 PUT THEM BACK ON AND RESUBMIT.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2. THE ENGINEER SHOULD
 TAKE HIS TITLE BLOCK OF THIS SHEET, AND
 DO NOT SIGN IF HE'S NOT THE DESIGNER AS
 INDICATED BY THE "STRUCTURAL ONLY"
 DISCLAIMER ON THE SEAL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL,
 I HAVE RETAINED THE ELECTRICAL SHEET
 FROM ONE SET OF THE PLANS.
  