2006-06-23 00:00:00 
 ****UNSAT ***
  
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE A NEW MAIN
 DISCONNECT IS BEING INDICATED, HOWEVER
 IS THIS A NETER/MAIN COMBO? IF NOT,
 PLEASE INDICATE THE MAIN AT THE METER
 LOCATION ON PLANS.
 ** PLEASE SEE PANEL INSIDE HOUSE IS
 STILL BE SHOWN AS A MCB PANEL WHICH IS
 PERMITTED, HOWEVER NOT REQUIRED NOW THAT
 THERE IS MAIN OUTSIDE. IF SHOWN ON
 PLANS, THEN A MCB WILL BE REQ'D.
  
 3) NOTE: PLEASE SEE MISSING RECEPT FOR
 2' FO WALL SPACE IN MASTER SUITE.
 210.52
  
 4) NOTE: PLEASE SEE SD OUTSIDE BEDRM #2
 AND #3 MUST BE 5'FROM RAG, AND 3' FROM
 BATH RM DOOR. PLEASE SEE MECH PLANS
 INDICATE THE SD IN THE RAG SPACE.
 IF SPACE IS CONSTRICTED, THE RAG MAY BE
 REQUIED TO BE MOVED, AS THE SD MUST BE
 OUTSIDE THE BEDRMS,BUT 3' FROM BATH DR.
 NFPA-72 11.8.3 2002
  
 5) NOTE: PLEASE SEE RISER IS MISSING THE
 SEC'S?
  
 6) NOTE: PLEASE SEE MISSING "EQUIPMENT
 GROUNDING CONDUCTOR" WHICH IS REQUIRED
 AFTER THE FIRST MEANS OF DISCONNECT.
 250.6,250.24B,250.110, SIZE PER 250.122
  
 7) NOTE: PLEASE SEE PANEL SHOWS WELL
 PUMP AS 2KW ON A 1-POLE 20A BRKR. PLEASE
 KNOW THE MAX VA PERMITTED ON THIS 20A
 CIRCUIT IS 1920VA.
 IS THIS NOT A 2-POLE 20A BRKR? PLEASE
 ADJUST.
 240.4,310.16,215.5 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  