| 2006-06-23 00:00:00 | |
| | ****UNSAT *** |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SEE A NEW MAIN |
| | DISCONNECT IS BEING INDICATED, HOWEVER |
| | IS THIS A NETER/MAIN COMBO? IF NOT, |
| | PLEASE INDICATE THE MAIN AT THE METER |
| | LOCATION ON PLANS. |
| | ** PLEASE SEE PANEL INSIDE HOUSE IS |
| | STILL BE SHOWN AS A MCB PANEL WHICH IS |
| | PERMITTED, HOWEVER NOT REQUIRED NOW THAT |
| | THERE IS MAIN OUTSIDE. IF SHOWN ON |
| | PLANS, THEN A MCB WILL BE REQ'D. |
| | |
| | 3) NOTE: PLEASE SEE MISSING RECEPT FOR |
| | 2' FO WALL SPACE IN MASTER SUITE. |
| | 210.52 |
| | |
| | 4) NOTE: PLEASE SEE SD OUTSIDE BEDRM #2 |
| | AND #3 MUST BE 5'FROM RAG, AND 3' FROM |
| | BATH RM DOOR. PLEASE SEE MECH PLANS |
| | INDICATE THE SD IN THE RAG SPACE. |
| | IF SPACE IS CONSTRICTED, THE RAG MAY BE |
| | REQUIED TO BE MOVED, AS THE SD MUST BE |
| | OUTSIDE THE BEDRMS,BUT 3' FROM BATH DR. |
| | NFPA-72 11.8.3 2002 |
| | |
| | 5) NOTE: PLEASE SEE RISER IS MISSING THE |
| | SEC'S? |
| | |
| | 6) NOTE: PLEASE SEE MISSING "EQUIPMENT |
| | GROUNDING CONDUCTOR" WHICH IS REQUIRED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | 250.6,250.24B,250.110, SIZE PER 250.122 |
| | |
| | 7) NOTE: PLEASE SEE PANEL SHOWS WELL |
| | PUMP AS 2KW ON A 1-POLE 20A BRKR. PLEASE |
| | KNOW THE MAX VA PERMITTED ON THIS 20A |
| | CIRCUIT IS 1920VA. |
| | IS THIS NOT A 2-POLE 20A BRKR? PLEASE |
| | ADJUST. |
| | 240.4,310.16,215.5 ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |