| Plan Review Notes For Permit 05120638 |
| Permit Number |
05120638 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-05-01 00:00:00 | | | | | | | THE SERVICE MUST COMPLY WITH THE | | | FOLLOWING: | | | | | | 230.70(A)(1). | | | (1) READILY ACCESSIBLE LOCATION. THE | | | SERVICE DISCONNECTING MEANS SHALL BE | | | INSTALLED AT A READILY ACCESSIBLE | | | LOCATION EITHER OUTSIDE OF A BUILDING OR | | | STRUCTURE OR INSIDE NEAREST THE POINT OF | | | ENTRANCE OF THE SERVICE CONDUCTORS. | | | | | | THE NOTE ABOUT "RUNNING OVERHEAD IN | | | TRUSSES" ON THE RISER DICTATES THAT A | | | MAIN DISCONNECT BE LOCATED OUTSIDE, | | | PREFERABLY BY THE METER. PLEASAE SHOW | | | SAME ON RISER AND LOCATE THE MAIN ON THE | | | PLAN. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|