| Plan Review Notes For Permit 05120609 |
| Permit Number |
05120609 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-12 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | | | 1- THIS IS A SIX STORY BUILDING. PROVIDE | | | ENGINEERING CALCULATIONS SHOWING WHAT | | | ARE THE UPLIFT LOADS REQUIRED TO BE | | | RESISTED BY THE CONCRETE TILE. SECTION | | | 106.1.2 OF CITY AMENDMENTS TO THE FBC | | | 2004. | | | | | | 2- SPECIFY HOW IS THE TILE FASTENED TO | | | MEET THE UPLIFT PRESSURES CALCULATED BY | | | THE ENGINEER. SEC. 106.1.2 CITY | | | AMENDMENTS TO FBC 2004. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|