| Plan Review Notes For Permit 05120547 |
| Permit Number |
05120547 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-03 00:00:00 | DENIED | | | | | | 1) CONSTRUCTION DOCUMENTS ARE REQUIRED | | | TO BE PREPARED BY A DESIGN PROFESSIONAL | | | PER FLORIDA STATUTES 481.229 AND | | | 471.003. | | | | | | 2) CITY AMENDMENTS TO FBC 106.1.1 | | | REQUIRES PLANS TO BE DIMENSIONED AND OF | | | SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED. THE PLANS THAT WERE SUBMITTED | | | DO NOT REFLECT THE DESCRIPTION OF WORK | | | ON THE PERMIT APPLICATION. | | | | | | 3) FBC 106.1.3 REQUIRES PLANS TO BE A | | | MINIMUM 1/8" SCALE. | | | | | | 4) TWO COMPLETE SETS OF PLANS ARE | | | REQUIRED PER FBC 106.1. | | | | | | 5) SPECIFY THE CONSTRUCTION TYPE FOR THE | | | BUILDING PER 2004 FBC SECTION 602. NOTE: | | | WOOD FRAMING IS NOT ALLOWED IN TYPE I OR | | | TYPE II CONSTRUCTION. | | | | | | 6) SPECIFY THE FIRE RATED ASSEMBLY THAT | | | WILL BE INSTALLED AT THE TENANT | | | SEPARATION WALLS. PROVIDE A WALL | | | SECTION. SPECIFY THE LISTING NUMBER AND | | | AGENCY FOR THE FIRE RATED ASSEMBLY. | | | | | | 7) FBC 1210.3 REQUIRES SHOWER | | | COMPARTMENTS AND WALLS ABOVE BATHTUBS | | | WITH INSTALLED SHOWER HEADS TO BE | | | FINISHED WITH NONABSORBENT SURFACES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|