Plan Review Notes
Plan Review Notes For Permit 05120532
Permit Number 05120532
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-30 00:00:00********** UNSAT **********
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3)NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
 CIRCUIT(S) SHALL BE 20A #12.
  
 4)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 NFPA-72 11.5.1.1
  
 5) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 6)NOTE: PLEASE SUBMIT A COMPLETE PANEL
 SCHEDULE, SHOWING ALL MIN CIRCUITS
 REQUIRED PER 2002 NEC.
 SMALL APPL, BATH(S), WASHER/DRYER ETC
 ETC.
 210.11,210.52,220.16, ETC.
 PLEASE SHOW OCP FOR EACH CIRCUIT AND AWG
 TO CORRELATE. 240.4,310.16
 215.5
  
 7)NOTE: PLEASE SUBMIT A LOAD
 CALCUALTIONS BASED ON 2002 NEC 220
  
 8)NOTE: PLEASE SEE ALL OUTSIDE RECEPTS
 SHALL BE GFI. 210.8A2
  
 9)NOTE: PLEASE SEE RISER MENTIONS MCB
 PANEL BACK TO BACK WITH METER, HOWEVER
 LAUNDRY RM SHOWS WHAT APPEARS TO BE TWO
 PANELS??
 215.5
  
 10)NOTE: PLEASE SEE FBC ADMINISTRATIVE
 SECTIONS, 106.3.4.3 WHICH REQUIES THE
 PERSON RESPONSIBLE FOR PLANS TO PRINT
 AND SIGN NAME.
 PLEASE BE SURE TO DRAW UP AS CLEAR AS
 POSSIBLE.
  
 11)NOTE: PLEASE SEE 210.70 FOR MISSING
 LT IN UTILITY RM.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  
 **
  
  
  
  
  
  