| 2006-12-20 19:39:07 | ** UNSAT ** |
| | |
| | 1) NOTE:NOTE OK, AS THE ELECTRICAL PERMIT WAS NOT |
| | AATCHED IN COMPUTER SYSTEM, PREVIOUS NOTE FOR 4X FEE |
| | AND HOLD REMOVED. |
| | |
| | |
| | 2) NOTE: PLEASE COMPLETE PHOTO-METRICS AS PARTIALLY |
| | SHOWN FOR HALLWAYS/EGRESS PATHS. |
| | PLEASE SEE MINIMUM LIGHTING LEVELS UNDER NORMAL AND |
| | EMERGENCY ARE REQUIRED. |
| | PLEASE SEE NFPA-101 2003 7.8, 7.9 |
| | PLEASE SEE ONLY A PARTIAL HALLWAY IS SHOWN FOR LIGHTING |
| | LEVELS WHICH ARE ONLY JUST OVER MINIMUM AND OTHER AREAS |
| | OF HALLWAYS NOT SHOWN CONTAIN LESS LIGHTING FIXTURES IS |
| | OF CONCERN TO THIS OFFICE. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |