| 2006-06-30 00:00:00 | *****UNSAT ***** |
| | 1ST REVIEW, ELECTRICAL PLANS NOW |
| | SUBMITTED. |
| | |
| | |
| | ** PLEASE KNOW, PLANS ARE STILL ONLY |
| | BEING SUBMITTED FOR "PLAN REVIEW" AND |
| | HAVE NOT SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1) NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCK FOR THE |
| | ARCHITECTURAL FIRM. FAC 61G1-16.004. |
| | PLEASE SEE MISSING THE PRINTED NAME AND |
| | LICENSE NUMBER OF ARCHITECT, AND MISSING |
| | THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | FOR ARCHITECTURAL FIRM. |
| | THIS IS REQUIRED ON ALL SHEETS |
| | CONTAINING A TITLE BLOCK FOR SADI FIRM. |
| | ** THIS IS REQUIRED FOR ALL TRADES AND |
| | FOR REVIEW WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE FS SHEETS SUBMITTED |
| | ARE NOT SIGNED,DATED, OR SEALED?? |
| | PLEASE KNOW, IF THESE ARE SUBMITTED AS |
| | PART OF THIS SETS FOR RECORD, EVEN IF |
| | THE FS ARE UNDER SEPARATE PERMIT, THE |
| | SHEETS SHALL BE SIGNED, DATED, AND |
| | SEALED. |
| | FS 471.025, FAC 61G15-23.002 |
| | |
| | 3) NOTE: PLEASE KNOW, WHEN THIS IS BEING |
| | SUBMITTED FOR PERMIT, THE COMPLETE VALUE |
| | FOR SCOPE OF WORK SHALL INCLUDE ALL |
| | LABOUR AND MATERIALS, WHETHER OR NOT ANY |
| | MATERIALS ARE OWNER SUPPLIED. |
| | FBC 108.3 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE SEE THAT CONDUCTOR TYPE |
| | SHALL BE INDICATED. |
| | 215.5, |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 5) NOTE: PLEASE PROVIDE PHOTO-METRICS |
| | FOR HALL WAYS. THIS CAN BE A TYPICAL |
| | DETAIL AND SECTION AS EACH FLR SEEMS |
| | TYPICAL. |
| | NFPA-101 7.8, 7.9 PLEASE SEE A MIN OF |
| | 1FT CANDLE SHALL BE PROVIDED UNDER |
| | NORMAL AND EMCONDITIONS. |
| | |
| | 6) NOTE: PLEASE SEE THAT NOW, EACH OF |
| | THESE UNITS HAVE BECOME "CONDOS", THE |
| | WASHER AND DRYER RECEPT CIRCUIT WIRING |
| | SHALL NOT BE INCLUDE ON THESE PLANS FOR |
| | SCOPE OF WORK. |
| | THE CALCULATIONS FOR THE ADDED LOAD TO |
| | EACH METER BACNK AND MAIN SERVICE SHOUDL |
| | REMAIN IN SETS. |
| | 215.5 |
| | |
| | 7) NOTE: PLEASE SEE PANEL LOCATIONS. |
| | UNABLE TO VERIFY WHICH SIDE OF THE |
| | PANELS SHOWN ARE THE ACCESSIBLE/OPENING |
| | SIDE. THE OPEING SIDE SHOULD ALL MEET |
| | 110.26 AND CORRELATE. |
| | 215.5 |
| | |
| | 8) NOTE: PLEASE SEE THAT THE ADDRESS FOR |
| | PROJECT SHALL BE INDICATED ON ALL |
| | SHEETS. |
| | FAC 61G1-16.004, FAC 61G15-23.002 |
| | PLEASE SEE ONLY THE "A" SHEETS CONTAINS |
| | AN ADDRESS OF 1830 EMBASSY DR. |
| | |
| | 9) NOTE: PLEASE SEE LOAD CALCULATIONS |
| | WHICH REFLECT NEC 220.84?? |
| | UNABLE TO LOCATED THIS REFERENCE IN THE |
| | CURRENT WE ARE UNDER IN THE STATE OF |
| | FLORIDA. |
| | NEC 2002 |
| | |
| | 10) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | THE FOLLOWING CODES. |
| | 2004 FBC, 2002 NFPA-70(NEC), 2002 |
| | NFPA-72, 2003 NFPA-101 |
| | |
| | 11) NOTE: PLEASE CLARIFY WHERE MAIN 1OF6 |
| | IS?? RISER SHOWS 2OF6, THRU 6OF6. |
| | 215.5 |
| | |
| | 12) NOTE: PLEASE SEE WHEN RESUBMITTING |
| | PLANS TO BE SURE AN MAKE TWO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. PLEASE SEE |
| | SOME ELECTRICAL SHEETS WERE IN SEPARATE |
| | SETS. |
| | 106.1.3 |
| | |
| | 13) NOTE: PLEASE BE SURE TO ADJUST SCOPE |
| | OF WORK ON APPLICATION AS THIS DOES NOT |
| | INCLUDE ALL THE REFEEDS TO HOUSE PANELS, |
| | "CONDO"PANELS AND METER BANKS. |
| | PLEASE SEE APPL MENTIONS INSTALLATION OF |
| | GFI RECEPTS, YET THESE COULD NOT BE |
| | LOCATED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |