| Plan Review Notes For Permit 05120430 |
| Permit Number |
05120430 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2006-03-31 00:00:00 | LOAD FOR AHU HEAT SHOULD HAVE BEEN | | | FIGURED AT 100%, HOWEVER SHOWN AT 65%. | | | EVEN IF FIGURED AT 100%, THE LOAD ON | | | GENERATOR WOULD STILL BE IN DESIGNED | | | LOAD. |
|