Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop E
Sequence Number 9
Notes
Date Text
2009-01-14 14:44:26 
  
  
 REVISION DENIED
  
 SAME COMMENTS AS THE PREVIOUS REVIEW:
  
 1} THE ENGINEER OF RECORD MUST SEAL THE DOCUMENTS WITH
 A SEAL ACCEPTABLE TO THE BOARD PER 61G15-23.001, AND
 ILLUSTRATED IN SAME.
  
 2} SHEET E-14 HAS A NOTE REGARDING ENCASING THE SERVICE
 CONDUIT AND INDICATES A DETAIL ON SHEET "20". IT IS NOT
 INDICATED WHICH SHEET "20", E, A, S, ETC. PLEASE
 INDICATE THE SHEET THIS DETAIL IS ON.
  
 NOTE: SEE 61G15-27.001, AND PRODUCE A LETTER FROM
 RONALD LARSON TO THIS DEPARTMENT , SIGNED, DATED AND
 SEALED BY HIM, NOT MR. DELAFOREST, OF HIS INTENT TO BE
 THE SUCCESSOR ENGINEER. IF MR. LARSON WILL NOT TAKE
 THAT RESPONSIBILITY THEN THE DESIGNER OF RECORD MUST
 SIGN, DATE AND SEAL ALL REVISIONS TO THE PLAN HE
 DESIGNED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  