| Plan Review Notes For Permit 05120429 |
| Permit Number |
05120429 |
|
| Review Stop |
P |
| Sequence Number |
7 |
|
| Notes |
| Date |
Text |
| 2007-09-15 15:45:50 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P-01 FLOW SCHEMATIC SHOWS NO WATER SUPPLY TO THE | | | TWO ESEW, THE LS-1 AND THE DWH-201. PLEASE CLARIFY. | | | SECTION 106.1.1. | | | | | | 2. SHT P-08 PLUMBING ISOMETRIC WATER RISER DIAGRAM DOES | | | NOT REFLECT THE PIPING SHOWN ON THE FLOW SCHEMATIC. THE | | | 2" PWC IS NOT SHOWN CONNECTING TO THE DWH-201 RISER | | | DIAGRAM.--ONE ESEW IS SHOWN WITH HOT WATER SUPPLY | | | ONLY. PLEASE CLARIFY. CORRELATE RISER AND FLOW | | | SCHEMATIC.--PLEASE INDICATE IS THERE IS A TEMPERING | | | VALVE FOR THE EMERGENCY SHOWERS OR DO THEY HAVE A | | | TEMPERING/ANTI-SCALD VALVE AT THE SHOWER. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|