2008-08-08 14:07:11REVIEW #: SHOP DRAWINGS
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHOP DRAWINGS HAVE BEEN SUBMITTED SHOWING
 MODIFICATIONS TO THE HVAC SECTION DETAIL C/M-02 AS
 SHOWN ON PAGE M-06. THE SIZES OF THE DUCTS SHOWN ON THE
 PLANS DO NOT CORRESPOND WITH THE SIZES SHOWN ON THE
 SHOP DRAWINGS. MODIFICATIONS TO SIGNED AND SEALED PLANS
 SHALL BE SUBMITTED AS REVISIONS TO THE PERMIT DRAWINGS
 AND SHALL BE SIGNED AND SEALED BY THE DESIGNER OF
 RECORD IN ACCORDANCE WITH FBCB 106.4
  
 2. SHOP DRAWINGS CONTAIN A NOTE STATING "PER SOUTH
 FLORIDA BUILDING CODE." THE SOUTH FLORIDA BUILDING CODE
 IS NO LONGER IN EXISTANCE AND HAS NEVER BEEN IN FORCE
 WITHIN THIS JURISDICTION. ALL WORK SHALL BE DESIGNED
 AND CONSTRUCTED IN ACCORDANCE WITH THE 2004 FLORIDA
 BUILDING CODE WITH 2005 AMENDMENTS.
  
 NOTE: SHOP DRAWINGS MAY BE USED TO PROVIDE ADDITIONAL
 INSTALLATION DETAILS BUT MAY NOT BE USED TO MODIFY THE
 OFFICIAL CONSTRUCTION DOCUMENTS. PLEASE ADDRESS THE
 ABOVE COMMENTS AND RESUBMIT.
  