Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop ENG
Sequence Number 7
Notes
Date Text
2009-04-20 12:49:47PLAN FAILED.
 PLAN REVIEWER: DEAN LAUDERMILK, ENG. SRVC. #
 561-494-1083, CONSTR. SRVC. # 561-805-6716
 1. CIVIL PLAN HAS NOT BEEN RESUBMITTED TO ENGINEERING
 SERVICES SINCE THE PLANS WERE APPROVED ON MARCH 3,
 2006. CIVIL PLAN IS ONLY APPROVED FOR A PERIOD OF 1
 YEAR AND THAT IS ONLY IF NO REVISIONS HAVE BEEN MADE.
 SOME SHEETS HAVE OVER 10 REVISIONS MADE FROM 04-21-06
 TO 01-14-09. PLUMBING PLAN SHOWS TWO SUMP PUMPS SERVING
 THE TRUCK SCALES ARE TIED TO THE BUILDINGS SANITARY
 SEWER SYSTEM, WHILE THE CIVIL SHEETS (5' OUTSIDE THE
 BUILDING) SHOW NO CHANGES TO THE SANITARY. RESUBMIT A
 MINIMUM OF FOUR FULL SETS OF CIVIL DRAWINGS TO
 ENGINEERING SERVICES FOR REVIEW. TWO OF THE SETS WILL
 BE RETURNED. IF MORE ARE REQUIRED (FOR PERMITTING) THEN
 SUPPLY MORE THAN 4 SETS. SEE ITEM 2 WHICH NEEDS TO BE
 SHOWN ON THE CIVIL PLANS.
  
 2. P-10 HAS A REVISION TO ALLOW TWO SUMP PUMPS TO BE
 INSTALLED TO PUMP (WHAT?) INTO THE BUILDINGS INTERIOR
 GRAVITY SYSTEM AND OUT INTO THE CITY'S SYSTEM. THERE IS
 NOT ENOUGH DETAIL IN THE PLANS TO SHOW PROOF THAT THE
 BUILDING IS WATER TIGHT AND NO RAIN WATER WILL GET INTO
 THE SYSTEM. THE ONLY WAY THIS SYSTEM CAN BE TIED TO THE
 CITY SYSTEM IS IF THE AREA IS ROOFED AND NO RAIN WATER
 CAN BE TRANSPORTED INTO THE SANITARY SEWER. THEN THE
 LIQUID WILL NEED TO GO VIA A WATER/OIL SEPARATOR
 (GREASE TRAP) AND THEN IT CAN BE DIRECTED TO THE CITY
 SYSTEM. THIS NEEDS TO BE SHOWN ON THE CIVIL PLAN SHEET
 SINCE IT IS OUTSIDE THE BUILDING FOOT PRINT.