| Plan Review Notes For Permit 05120429 |
| Permit Number |
05120429 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-03-14 14:29:01 | | | | PROVISO!!!THESE COMMENTS TO BE ADDRESSED BY 5/1/07 | | | JLEAHY | | | | | | PAGE E-02RISER NOTES, MISSED ON THE PAST REVIEW. | | | | | | THE MAIN FEEDERS COMMING INTO THE BUILDING SHOW A 2/0 | | | GND????? | | | | | | IF THIS GROUND IS THE NEUTRAL THEN YOU NEED TO IDENTIFY | | | IT AS SUCH. | | | | | | 250.24(B) (1) STATES THE MINIMUM IS BASED ON NOT | | | SMALLER THAN THE REQUIRED | | | GROUNDING ELECTRODE WHICH WOULD BE A 3/0 BASED ON | | | 250.66??? | | | | | | YOUR MAIN SERVICE ENTRANCE CONDUCTORS SHOW GND. AND | | | YOUR SUBFEEDS SHOW GND | | | WHICH ONES ARE NEUTRALS AND WHICH ARE EQUIPMENT | | | GROUNDING CONDUCTORS? | | | NEED TO REIDENTIFY ALL NEUTRAL CONDUCTORS AS SUCH, AND | | | NOT AS A GROUND | | | | | | I DID NOT NOTICE THE NOTE FOR EM1, AND EM2 UNTIL YOU | | | CHANGED THEM. | | | LIGHTS IDENTIFIED AS EM1 AND EM2HAVE NO CIRCUIT | | | NUMBERS SHOWN FOR THE BRANCH CIRCUITS. | | | THE NOTE TO CONNECT TO THE NEAREST CIRCUIT DOES NOT | | | WORK FOR LOADING OF THE BRANCH CIRCUITS. | | | PLEASE DESIGNATE CIRCUIT NUMBERS ON PLANS.ADJUST | | | LOADS ON PANEL SCHEDULES. | | | | | | NEED GENERATOR SPECS AND TRANSFER SWITCH SPECS FOR | | | REVIEW | | | | | | QUESTIONS CALL JAKE 805-6740 |
|