| 2007-01-05 18:58:24 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW. COMMENT NUMBER |
| | SHALL REMAIN THE SAME FOR CLARITY: |
| | |
| | 4. OK |
| | 8. OK |
| | |
| | 9. SHT A-10 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE BEING DRAINED BY EACH |
| | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS IN |
| | CALCULATIONS. - SHOW THE LOCATION OF ALL |
| | OVERFLOW SCUPPERS, AND SIZE OF O/F |
| | SCUPPERS PER SECTIONS 1101.7, 1107.3 AND |
| | TABLE 1106.7. THE SIZING OF THE SCUPPERS |
| | CAN NOT BE DETERMINED WITHOUT REFERENCE |
| | TO THE DEFLECTION OF THE ROOF. PLEASE |
| | SHOW O/F SCUPPER CALCULATION ON PLANS |
| | INDICATING SIZE OF SCUPPERS AND PROVIDE |
| | DETAIL OF O/F SCUPPERS SHOWING HEIGHT |
| | AND WIDTH. |
| | ***RESPONSE NOTED, BUT THE EMERGENCY |
| | OVERFLOW SCUPPERS ARE REQUIRED PER |
| | SECTION 1107.1. PLEASE SIZE SCUPPERS PER |
| | SECTIONS AND TABLE REFERENCED ABOVE AND |
| | SHOW THE LOCATION OF ALL SCUPPERS. ALSO |
| | SEE SECTION 1503.4.3. SUBMIT A DETAIL |
| | FOR EMERGENCY OVER FLOW SCUPPERS. SHOW |
| | SCUPPERS ON EXTERIOR ELEVATIONS FOR |
| | BUILDING. |
| | ******RESPONSE NOTED, BUTSEPARATE SYSTEMS ARE |
| | REQUIRED. THE PRIMARY SCUPPERS ARE INDICATED AS 2 - |
| | 12"X24"OPENINGS, AND THE OVERFLOWSCUPPERS ARE |
| | INDICATED AS THE SAME. PLEASE CLARIFY. PLEASE SUBMIT A |
| | DETAIL OF THE LEADER BOX. SHOW THE ELEVATIONS FROM THE |
| | FRONT AND THE SIDE TO INDICATE WHERE THE SECONDARY |
| | SCUPPER DRAINS.-DOWNSPOUTS (2) ARE INDICATED IN THE |
| | CALCULATIONS, BUT (4) ARE SHOWN ON THE ROOF PLAN. SHT |
| | A-21, DETAIL 12 PLEASE INDICATE THE SIZE OF THE |
| | DOWNSPOUT. |
| | |
| | 11. OK |
| | 13. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | |
| | 19. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | G. OK |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE NOTED. |
| | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR |
| | THE INDUSTRIAL FURNACE/DRYER IS REQUIRED SHOWING THE |
| | LISTING AND BTU LOAD. |
| | |
| | 21. OK |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. OK |
| | |
| | 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS |
| | FOR THE REGULATORS USED. |
| | INDICATE IF THE REGULATOR WILL BE VENTED |
| | AND IF SO INDICATE THE MATERIAL USED FOR |
| | THE VENT. ALSO SHOW VENTING ROUTE FOR |
| | REGULATOR. SECTION 106.1.1. |
| | ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATION |
| | SHEETS FOR THE REGULATORS ARE REQUIRED. PLEASE INDICATE |
| | MODEL NUMBER BEING USED FOR EACH REGULATOR. |
| | |
| | 3B. OK |
| | 4B. OK |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |