Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop P
Sequence Number 3
Notes
Date Text
2007-01-05 18:58:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME FOR CLARITY:
  
 4. OK
 8. OK
  
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 ***RESPONSE NOTED, BUT THE EMERGENCY
 OVERFLOW SCUPPERS ARE REQUIRED PER
 SECTION 1107.1. PLEASE SIZE SCUPPERS PER
 SECTIONS AND TABLE REFERENCED ABOVE AND
 SHOW THE LOCATION OF ALL SCUPPERS. ALSO
 SEE SECTION 1503.4.3. SUBMIT A DETAIL
 FOR EMERGENCY OVER FLOW SCUPPERS. SHOW
 SCUPPERS ON EXTERIOR ELEVATIONS FOR
 BUILDING.
 ******RESPONSE NOTED, BUTSEPARATE SYSTEMS ARE
 REQUIRED. THE PRIMARY SCUPPERS ARE INDICATED AS 2 -
 12"X24"OPENINGS, AND THE OVERFLOWSCUPPERS ARE
 INDICATED AS THE SAME. PLEASE CLARIFY. PLEASE SUBMIT A
 DETAIL OF THE LEADER BOX. SHOW THE ELEVATIONS FROM THE
 FRONT AND THE SIDE TO INDICATE WHERE THE SECONDARY
 SCUPPER DRAINS.-DOWNSPOUTS (2) ARE INDICATED IN THE
 CALCULATIONS, BUT (4) ARE SHOWN ON THE ROOF PLAN. SHT
 A-21, DETAIL 12 PLEASE INDICATE THE SIZE OF THE
 DOWNSPOUT.
  
 11. OK
 13. OK
 15. OK
 16. OK
 17. OK
 18. OK
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE INDUSTRIAL FURNACE/DRYER IS REQUIRED SHOWING THE
 LISTING AND BTU LOAD.
  
 21. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATION
 SHEETS FOR THE REGULATORS ARE REQUIRED. PLEASE INDICATE
 MODEL NUMBER BEING USED FOR EACH REGULATOR.
  
 3B. OK
 4B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]