Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop M
Sequence Number 3
Notes
Date Text
2006-11-17 10:46:36PROVISO:
  
 PLAN SHEET M-06,DETAIL F & G, DETAIL DOES NOT
 INDICATE HEIGHT OF THE ROOF CURB.PER 2004 FBC 1509.7,
 ROOF MOUNTED MECHANICAL EQUIPMENT SHALL BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8 INCHES ABOVE THE ROOF
 SURFACE.
  