| Plan Review Notes For Permit 05120429 |
| Permit Number |
05120429 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-11-28 18:11:45 | PAGE E-02,E-03, AND E-04 LOAD CALCULATIONS ARE NOT | | | DETAILED ENOUGH | | | | | | PLEASE SHOW HOW LOADS ARE CALCULATED. | | | | | | WHEN I DID THE MCC'S PG. E-02,03,I CAME OUT WITH MORE | | | THAN 1200 AMPS FOR EACH? | | | | | | THIS WOULD MAKE THE BUSS TOO SMALL. | | | | | | THE CALCULATION WAS DONE PER 430.24. | | | | | | PLEASE SHOW HOW LOADS WHERE CALCULATED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|