2006-11-28 18:11:45PAGE E-02,E-03, AND E-04 LOAD CALCULATIONS ARE NOT
 DETAILED ENOUGH
  
 PLEASE SHOW HOW LOADS ARE CALCULATED.
  
 WHEN I DID THE MCC'S PG. E-02,03,I CAME OUT WITH MORE
 THAN 1200 AMPS FOR EACH?
  
 THIS WOULD MAKE THE BUSS TOO SMALL.
  
 THE CALCULATION WAS DONE PER 430.24.
  
 PLEASE SHOW HOW LOADS WHERE CALCULATED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  