Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop B
Sequence Number 3
Notes
Date Text
2006-12-26 10:48:40****CORRECTIONS****
 ****CONVERTED TO PERMIT; SECOND PERMIT
 PLAN REVIEW ****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER 561-805-6724
 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004EXISTING BUILDING
 CODE
 FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE
 FBC2004
  
 COMMENTS FROM PREVIOUS REVIEW, EITHER
 NOT ADDRESSED OR REQUIRING FURTHER
 CLARIFICATION; NUMBERING REMAINING THE
 SAME FOR CONSISTENCY:
  
 1.)REGARDING IMPACT FEES, PLEASE SUBMIT A LETTER
 CONFIRMING THAT THE BUILDING IS OWNED BY SOLID WASTE
 AUTHORITY.NOTE THAT PRIVATELY OWNED COMPANIES
 OPERATING ON GOVERNMENT PROPERTY ARE NOT AUTOMATICALLY
 EXEMPT FROM IMPACT FEES.THE PURPOSE OF THE LETTER IS
 TO DOCUMENT EXEMPTION TO IMPACT FEES FOR THIS PROJECT.
  
  
 2.-3.)ADDRESSED.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA (INSPECTION
 SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 THE RESPONSE THAT THIS WILL BE DONE IS ACKNOWLEDGED.
 THIS IS REQUIRED PRIOR TO
 PERMIT ISSUANCE.NOTE THAT AS OF 12/21, MR. PISKURA
 HAS NOT ADVISED THAT THIS HAS BEEN RESOLVED.PLEASE
 CONTACT HIM AS SOON AS POSSIBLE TO PREVENT PERMITTING
 DELAYS.THE RESPONSE LETTER STATED THAT YOU WOULD
 SCHEDULE THE MEETING PRIOR TO INSPECTIONS.NOTE THAT
 THE REQUIREMENT IS TO HAVE AN INSPECTOR APPROVED BY THE
 CITY PRIOR TO PERMIT ISSUANCE.
  
 5-7.)ADDRESSED WITH EXCEPTION OF H4 OCCUPANCY
 CLASSIFICATION FOR CORROSIVE CHEMICAL USED INSIDE THE
 BUILDING; SEE OTHER COMMENTS.
  
 8.)REGARDING THE CODE SUMMARY, PLEASE NOTE THE
 FOLLOWING:
  
 A.)A01 WAS REVISED BUT STILL REFERS TO A ONE STORY
 BUILDING.AS PER CONVERSATIONS WITH ARCHITECT,
 ARCHITECT?S RESPONSE LETTER, AND COMMENTS FROM PREVIOUS
 REVIEWS, THIS IS A TWO STORY BUILDING (NOT A ONE STORY
 WITH A MEZZANINE AREA).PLEASE REVISE.
  
 B.)THE TABULAR OCCUPANT LOAD STATES THAT SECOND FLOOR
 F ACCESSORY IS 1536 SF, 100 SF PER OCCUPANT, FOR
 OCCUPANT LOAD OF 5.THE MATH IS INCORRECT, PLEASE
 REVISE.THE OCCUPANT LOAD FOR MEANS OF EGRESS CANNOT
 BE LESS THAN FBC TABLE 1004.1.2, SEE FBC1004.1.YOU
 CAN DECLARE AN OCCUPANT LOAD WHICH IS LESS THAN THE
 TABLE FOR PURPOSES OF EXCEPTION FROM VERTICAL
 ACCESSIBILITY REQUIREMENTS, BUT THIS IS NOT APPLICABLE
 FOR MEANS OF EGRESS.
  
 C.)SECOND FLOOR F ACCESSORY, SEE FBC302.2.FIRE
 BARRIER REQUIRED FOR ACCESSORY USE IF THE AREA EXCEEDS
 TEN PERCENT OF THE FLOOR AREA.THIS AREA IS 28%.THE
 CODE SUMMARY INDICATES THAT A 2 HOUR SEPARATION IS
 REQUIRED BUT NONE IS SHOWN BETWEEN THE ACCESSORY AREA
 AND THE CORRIDOR, WHICH THE BUSINESS AND FACTORY AREAS
 BOTH USE AS A MEANS OF EGRESS.
  
 D.)M02, IF PLANS ARE REVISED TO REQUIRE THE WALL
 BETWEEN THE CORRIDOR AND THE ACCESSORY AREA IS TO BE
 FIRE RATED, PENETRATIONS ARE TO BE PROTECTED FBC712.
  
 E.)A001 HAS A NOTE THAT THE SECOND FLOOR OCCUPANT
 LOAD WILL BE LESS THAN 50.NOTE THAT IF YOU USE THE
 SQUARE FOOT PER OCCUPANT DECLARED ON A001, THE OCCUPANT
 LOAD WILL BE GREATER THAN 50.HOWEVER, SEE FBC TABLE
 1004.1.2.ACCESSORY STORAGE AREAS, MECHANICAL
 EQUIPMENT ROOM, CAN BE 300 SF PER OCCUPANT.
  
 F.)IN CALCULATING OCCUPANT LOAD, ALL NUMBERS SHOULD
 BE ROUNDED UP AS THE OCCUPANT LOAD CANNOT BE LESS THAN
 FBC TABLE 1004.1.2.SEE FBC1004.1.
  
 9-12.)ADDRESSED.
  
 13.)THE ACCESSIBLE ROUTE FBC11-4.1.2(1) IS SHOWN.
 PLEASE CLARIFY HOW THE ACCESSIBLE ROUTE IS AFFECTED BY
 THE SLIDING GATE.HOW DOES THIS GATE OPERATE; IS THAT
 FUNCTION DIFFERENT FOR ACCESSIBILITY?THE SLOPE AND
 CROSS SLOPE ARE TO COMPLY WITH FBC11-4.3.7.
  
 14.)PROVIDE FIRE SPRINKLER PLANS, FBC*106.3.5.1.1(5).
 A SHEET SHOWING THE TYPE OF SPRINKLERS WHICH WILL BE
 INSTALLED IN EACH AREA WAS PROVIDED BUT DOES NOT COMPLY
 WITH STATUTORY REQUIREMENTS FS553.79(2).YOUR REQUEST
 THAT THIS BE A PROVISO ITEM IS ACKNOWLEDGED BUT PER
 BUILDING OFFICIAL STATUTORY REQUIREMENTS CANNOT BE
 PROVISO ITEMS.PLEASE SEE ATTACHED LETTER FROM THE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS (REGULATORY
 AGENCY FOR BUILDING CODE).IT STATES ?PLEASE NOTE THAT
 DESIGN DOCUMENTS, INCLUDING THE FIRE PROTECTION
 SPRINKLER SYSTEM (WHICH IS TO BE REVIEWED BY THE
 APPROPRIATE FIRE SAFETY INSPECTOR) ARE TO BE SUBMITTED
 TO YOU AT THE TIME OF PERMITTING, AND THAT THOSE
 DESIGNS MUST BE REVIEWED FOR COMPLIANCE AT THAT TIME
 BEFORE A PERMIT IS ISSUED.?CALCULATIONS, SPEC
 SHEETS, SHOPS, ETC. ARE NOT REQUIRED AT THIS TIME; THEY
 ARE TO BE SUBMITTED WITH THE FIRE SPRINKLER PERMIT
 APPLICATION.
  
 15.)ADDRESSED.
  
 16.)THE LIFE SAFETY PLAN APPEARS CODE COMPLIANT FOR
 F3 OCCUPANCY WITH THE EXCEPTION OF THE ITEMS NOTED
 BELOW.SEE OTHER COMMENTS REGARDING H4 OCCUPANCY. NOTE
 THAT IF H4 IS DETERMINED FOR A PORTION OF THE BUILDING,
 TRAVEL DISTANCE IS LIMITED TO 100FEET AND THE LIFE
 SAFETY PLAN WOULD NOT BE COMPLIANT FOR THAT OCCUPANCY
 CLASSIFICATION.
  
 A.)SPECIFY THE SLOPE FOR THE SLUDGE RECEIVING AREA.
 THIS AREA IS SHOWN AS A MEANS OF EGRESS.FEE
 FBC1003.5; DOES THIS REQUIRE A RAMP TO COMPLY WITH
 FBC1010?SEE ALSO FBC TABLE 1018.2.
  
 B.)DECLARE OCCUPANT LOAD FOR EACH AREA.OCCUPANT
 LOAD FOR MEANS OF EGRESS CANNOT BE LESS THAN FBC TABLE
 1004.1.2, SEE FBC1004.1.YOU CAN DECLARE AN OCCUPANT
 LOAD WHICH IS LESS THAN THE TABLE FOR PURPOSES OF
 EXCEPTION FROM VERTICAL ACCESSIBILITY REQUIREMENTS, BUT
 THIS IS NOT APPLICABLE FOR MEANS OF EGRESS.
  
 C.)THE BUSINESS AREA EXITS THROUGH THE CORRIDOR WHICH
 IS A PART OF THE F3 OCCUPANCY.SEE PREVIOUS LISTS IN
 REGARDS TO EXITING THROUGH A MORE HAZARDOUS OCCUPANCY.
 NOTE THAT THE CORRIDOR IS NOT FIRE RATED AND IS A PART
 OF THE F3 OCCUPANCY, NOT THE B OCCUPANCY.
  
 17-20.) ADDRESSED.
  
 21.)A MEZZANINE IS TO BE LOCATED IN A ROOM.
 AS THE AREA BELOW AND AREA ABOVE ARE
 BOTH ENCLOSED, THIS PORTION IS TWO
 STORIES.SEE THE DEFININTIONS FOR
 MEZZANINE AND STORY.THIS IS NOT
 LOCATED BETWEEN THE FLOOR BELOW AND THE
 CEILING ABOVE AS THE CEILING ABOVE THE
 SLUDGE STORAGE ROOM (WHICH HAS A WALL)
 IS THE 2ND FLOOR.THIS AREA IS TWO
 STORIES, NOT A MEZZANINE, BY DEFINITION.
  
 PLEASE REVISE A001 TO DECLARE A TWO STORY BUILDING.
  
 22.)ADDRESSED.
  
 23.)PRODUCT APPROVALS:
  
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED FOR
 ALL PRODUCTS, INCLUDING FOR PRODUCTS WHICH HAVE AN NOA.
 PLEASE PRINT THE FLORIDA STATE PRODUCT APPROVAL FROM
 THE WEBSITE FOR THE FOLLOWING NOAS:03-1015.05,
 05-0214.02, 03-0422.05, 03-1027.01, 03-0611.01.IF A
 FLORIDA STATE PRODUCT APPROVAL IS NOT AVAILABLE PLEASE
 ADVISE AND A LOCAL PRODUCT APPROVAL WILL BE ISSUED FOR
 YOU.
  
 DESIGN PRESSURES FOR THE WINDOWS WERE NOT PROVIDED ON
 THE PLAN, SHEET S01.
  
 NOA 05-0729.04 IS SMALL MISSILE IMPACT RATED.LARGE
 MISSILE IMPACT REQUIRED FOR THE FIRST THIRTY FEET ABOVE
 GRADE, FBC1609.1.4.IS THIS PRODUCT BEING INSTALLED
 OVER 30 FEET?PLEASE NOTE ON THE PRODUCT APPROVAL TO
 AVOID CONFUSION IN THE FIELD.OTHERWISE IMPACT
 PROTECTION IS REQUIRED.USE OF REMOVABLE SHUTTERS ON
 COMMERCIAL BUILDINGS MUST BE APPROVED BY THE BUILDING
 OFFICIAL.PLEASE ADVISE.
  
 THE PROPOSAL FROM WILLARD SHUTTER COMPANY IS FOR 120
 MPH WIND LOAD.IS THIS FASTEST MILE OR 3 SECOND GUST?
 CITY OF WEST PALM BEACH IS IN THE 140MPH WIND ZONE. SEE
 FBC1609.3.ENGINEERING AND SHOP DRAWINGS WILL BE
 REQUIRED PRIOR TO INSTALLATION.
  
 NOA 03-0827.11 GAF SELF ADHERING MODIFIED HAS A DESIGN
 PRESSURE LIMITATION OF -72.5, GENERAL LIMITATION #9,
 AND IS NOT COMPLIANT FOR ZONES 2 AND 3.
  
 NOA 02-0515.02, GENERAL LIMITATION #3, INSTALLER SHALL
 BE APPROVED BY GAF MATERIAL CORP.PLEASE ADDRESS.
  
 NOA 02-1018.11, BARRETT RAM-TOUGH PLAZA, INSTALLER
 SHALL BE APPROVED BY BARRETT.PLEASE ADDRESS.
  
 ANY PRODUCT APPROVALS NOT SUBMITTED AND REVIEWED PRIOR
 TO PERMIT ISSUANCE WILL BE REQUIRED TO HAVE SEPARATE
 PERMITS FOR THOSE ITEMS WITH SEPARATE FEES.
  
 24.)YOUR RESPONSE THAT THE SLUDGE RECEIVING AND
 SLUDGE STORAGE AREAS ARE EXEMPT FROM VERTICAL
 ACCESSIBILITY IS ACKNOWLEDGED.PLEASE SHOW A DESIGN
 OCCUPANT LOAD OF LESS THAN 5 FOR BOTH OF THESE AREAS ON
 SHEET A001.NOTE THAT YOUR OCCUPANT LOAD FOR EGRESS
 WILL BE GREATER THAN 5 BASED ON SQUARE FOOT AREA.
  
 25-29.)ADDRESSED.
  
 30.)PROVIDE DETAILS FOR THE UL
 ASSEMBLIES SPECIFIED.A05 STATES ?INDICATE 2-HOUR
 RATED ASSEMBLIES (SEE FBC TABLE 7720.1(2) FOR
 EQUIVALENCE OF FIRE RESISTANCE RATING OF SOLID
 CONCRETE)?.THIS IS NOT A CORRECT CODE REFERENCE.
 PROVIDE A DETAIL.IF YOU ARE USING CALCULATED FIRE
 RESISTANCE, PROVIDE COMPONENTS ALONG WITH TIME ASSIGNED
 TO EACH COMPONENT TO SHOW COMPLIANCE WITH THE SPECIFIED
 2 HOUR RATING.
  
 31.)ADDRESSED.
  
 32.)FROM THE PREVIOUS LISTS:PROVIDE ALL STRUCTURAL
 INFORMATION AT THIS TIME FOR ITEMS SUCH AS THE DUSTROL
 TANK;
 LOADS, CONCRETE, ANCHORING,
 FBC415.7.2.2, TANK PROTECTION), NFPA30
 (STORAGE OF COMBUSTIBLES), FBC1606.1.3
 (ANCHORING TO PREVENT OVERTURNING).SEE
 ALSO FBC415.7.1.1, AND FBC415.7.1.5,
 GRAIN ELEVATORS AND SIMILAR STRUCTURES;
 THIS APPEARS TO APPLY TO THE STORAGE
 SILO (PROVIDE INFORMATION IN REGARDS TO CONSTRUCTION
 TYPE, HEIGHT).
  
 THIS WILL BE A PROVISO ITEM AS REQUESTED.CHANGES TO
 THE PLAN SUCH AS CONCRETE SLABS NOT CURRENTLY SHOWN ON
 THE PLAN WILL REQUIRE A REVISION WITH APPLICABLE FEES.
 OTHER ITEMS SUCH AS SHOP DRAWINGS AND ENGINEERING FOR
 ITEMS SUCH AS THE TANKS AND SILO WILL BE SUBMITTALS (NO
 FEE).
  
 33-36.) ADDRESSED.
  
 37-38, 43, 46)REGARDING OCCUPANCY CLASSIFICATION,
 PLEASE PROVIDE QUANTITY OF CORROSIVE CHEMICALS WHICH
 WILL BE USED IN THE PROCESSING AREA.BASED ON A
 TELEPHONE CONVERSATION WITH MR. DELAFOREST AND THE
 RESPONSE LETTER, THE QUANTITY IS LESS THAN THE EXEMPT
 AMOUNT AND DOES NOT CHANGE THE OCCUPANCY CLASSIFICATION
 FROM F3 TO H4.PLEASE NOTE THE QUANTITY OF CORROSIVE
 CHEMICAL TO BE USED IN THE PROCESSING AREA ON THE PLAN
 OR PROVIDE A SIGNED, SEALED, AND DATED CLARIFICATION
 LETTER.
  
 39-42.) ADDRESSED.
  
 44-45.) ADDRESSED.
  
 47.)ADDRESSED.
  
 48.) C12, ACCESSIBLE PARKING, THE FEE IS
 $250 RATHER THAN $100, CITY OF WEST PALM
 BEACH RESOLUTION #390-03, SECTION 2, #D.
  
 PLEASE REVISE.
  
 49-57.) ADDRESSED.
  
 58.)OCCUPANT LOAD SHOULD ROUND UP RATHER THAN ROUND
 DOWN WHEN CALCULATIONS RESULT IN A FRACTION AS THE LOAD
 CANNOT BE LESS THAN THE TABLE FBC1004.1.2.
  
 59-74.) ADDRESSED.
  
 NEW COMMENTS:
  
 75.)THE FIRE RATED WALLS SHOWN ON A001A AND A04 ARE
 NOT CONSISTENT.THE 2 HOUR WALL WHICH PROTECTS THE
 EXTERIOR STAIR IS SHOWN AS EXTENDING 10FT ON EITHER
 SIDE OF THE STAIR ON A001A, BUT ON A04 THE STAIRWAY
 ONLY IS RATED.IT IS NOT CLEAR WHETHER OR NOT DOOR
 103.1 IS REQUIRED TO BE RATED.THE DOOR SCHEDULE ON
 A22 SPECIFIES A NON RATED DOOR, SHEET A001A SHOWS THIS
 OPENING INCLUDED IN THE 10FT FIRE RATED WALL AREA. FIRE
 RESISTANCE RATING OF 1.5 HOUR REQUIRED FOR 2 HOUR WALL,
 FBC715.3.
  
 76.)A001B SHOWS A WINDOW AT THE BREAK ROOM WHICH IS
 TO BE FIRE RATED.SPECIFY OPENING PROTECTION AND
 PROVIDE A PRODUCT APPROVAL.IMPACT PROTECTION
 REQUIRED.
  
 77.)A001A SHOWS A SECOND EXTERIOR STAIR TO THE EAST
 OF STAIR 1.THIS STAIR DOES NOT APPEAR ON A04 OR ON
 OTHER SHEETS.
  
 78.)PLEASE CONFIRM THAT THEPERMIT APPLICATION TO
 REFERS TO THE CORRECT PARCEL ID 74424234000001000.
  
 79.)S18, TILT UP PANEL NOTES, ITEM 13, WRONG CODE
 REFERENCE FOR IMPACT.DESIGN CRITERIA IS REQUIRED BUT
 CODE REFERENCES ARE NOT REQUIRED ON THE PLANS.YOU MAY
 EITHER REVISE THE CODE REFERENCE OR REMOVE IT.
  
 80.)S01, IT IS NOT CLEAR WHAT ROOF ENCLOSURE
 PRESSURES ARE FOR.IS THIS THE CHEMICAL STORAGE
 ENCLOSURE, WHICH NO LONGER HAS A ROOF?
  
 81.)THE DETAIL FOR THE 2 HOUR FLOOR/CEILING ASSEMBLY
 SPECIFIES A 4" POURED CONCRETE TOPPING; OTHER PAGES ON
 THE PLAN SPECIFY 2".PLEASE ADDRESS.
  
  
  
  
  
  