| 2009-09-16 16:33:30 | REVISION, SHEET S23 OK |
| | |
| | ****CORRECTIONS - REVISION, S20 AND ROOF HATCH PRODUCT |
| | APPROVAL*** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2004 |
| | |
| | 1. A DETAIL WAS ADDED TO THE SCRUBBER FOUNDATION WHICH |
| | IS LABLED "EQUIPMENT ACCESS WALKWAY." IS THIS THE STAIR |
| | AND WALKWAY WHICH IS TO BE A PART OF THE EXIT PATH TO |
| | THE PUBLIC WAY? IT IS MY UNDERSTANDING THAT THERE IS AN |
| | EXIT DOOR WHICH HAS ACCESS TO THE PUBLIC WAY BLOCKED BY |
| | PIPING, AND A STAIR WAS TO BE PROVIDED TO FACILITATE |
| | EXITING. PLEASE REVISE DRAWING TO PROPERLY LABEL THIS |
| | MEANS OF EGRESS STAIR/WALKWAY AND INCORPORATE THE NEW |
| | MEANS OF EGRESS COMPONENT INTO THE LIFE SAFETY PLAN. |
| | SEE FBC1002, DEFINITION OF MEANS OF EGRESS. SEE |
| | FBC1003.6, MEANS OF EGRESS CONTINUITY. |
| | |
| | 2. FBC1003.5, CHANGES IN LEVEL IN THE MEANS OF EGRESS |
| | SHALL BE BY EITHER A RAMP OR STAIR. SEE OTHER COMMENTS. |
| | |
| | 3. PROVIDE A STRUCTURAL DETAIL FOR THE PROPOSED |
| | CONSTRUCTION, FBC16. ONLY A PLAN VIEW WITH HORIZONTAL |
| | DIMENSIONS WAS PROVIDED. A DIMENSIONED SECTION AND |
| | ELEVATION SHOULD BE PROVIDED TO SHOW COMPLIANCE WITH |
| | THE REQUIREMENTS OF FBC CHAPTER 10. |
| | |
| | 4. SHOW THE DOOR AND DOOR SWING FOR THE EXIT WHICH THIS |
| | WALKWAY SERVICES. DOOR IS NOT TO OBSTRUCT THE PATH OF |
| | TRAVEL, HAS THE EQUIPMENT AND PIPING AFFECTED THE DOOR |
| | SWING? SEE C9; IT APPEARS THAT THE PROPOSED STAIR IS |
| | OBSTRUCTED BY THE EXIT DOOR, AND THE DOOR SWING IS |
| | OBSTRUCTED BY THE PROPOSED STAIR. PLEASE INCORPORATE |
| | INTO THE LIFE SAFETY PLAN AND REVERSE DOOR SWING IF |
| | NECESSARY. |
| | |
| | 5. IN THE DETAIL, PROVIDE DETAILS WITH DIMENSIONS WHICH |
| | SHOW COMPLIANCE WITH: |
| | |
| | 1003.3, PROTUDING OBJECTS |
| | 1005.1, EGRESS WIDTH (MAINTAINING MINIMUM |
| | HEIGHT/PROTUDING OBJECT REQUIREMENTS) |
| | 1006.1, MEANS OF EGRESS ILLUMINATION |
| | 1006.1.3, SHOW LEVEL OF ILLUMINATION |
| | 1008.1.5, LANDING SIZE |
| | 1009, STAIR DIMENSIONS (RISE AND RUN, CLEARANCE, ETC.) |
| | 1009, HANDRAILS (PROVIDE A DETAIL); NOTE THAT HANDRAILS |
| | ARE SHOWN ON THE PLAN BUT NO EXTENSIONS SHOWN, |
| | 1009.11.5 |
| | 1012, GUARDRAILS - PLAN SHOWS THREE RISERS, BUT A NOTE |
| | ON THE PLAN STATES THAT THE WALKWAY WILL NOT BE MORE |
| | THAN 4', SO IT IS NOT CLEAR IF GUARDRAILS ARE REQUIRED |
| | - ELEVATION OR SECTION SHOULD SHOW HEIGHT ABOVE GRADE |
| | 1009.5, DETAIL STATES THAT WALKWAY IS CONSTRUCTED OF |
| | P.T. LUMBER; THIS BUILDING IS A TYPE IIB, NON |
| | COMBUSTIBLE BUILDING. CONSTRUCTION OF MEANS OF EGRESS |
| | STAIRS TO BE CONSISTENT WITH BUILDING TYPE, NON |
| | COMBUSTIBLE REQUIRED |
| | |
| | 6. ONE SET OF A ROOF HATCH PRODUCT APPROVAL WAS |
| | SUBMITTED. DON'T YOU NEED A SET FOR INSPECTION |
| | PURPOSES? |
| | |
| | 7. PLEASE REVISE SHEET A21 WHICH DEPICTS AN ALUMINUM |
| | ROOF HATCH. |
| | |
| | 8. A21 SHOWS A 60" ROOF HATCH, BUT THE ATTACHMENT |
| | CALCULATIONS IN THE PRODUCT APPROVAL ARE FOR A 36" ROOF |
| | HATCH. THE MANUFACTURER'S SPEC SHEET SUBMITTED DOES NOT |
| | INCLUDE THE JOB SPECIFIC INFORMATION; WIDTH & LENGTH |
| | AND PART NUMBER. IS THIS A RHG3630T OR RHG3636T? IF THE |
| | ROOF HATCH TO BE INSTALLED IS NOT 37X43 FRAME SIZE, |
| | THEN AN ENGINEERED SPECIFICATION FOR INSTALLATION WILL |
| | BE REQUIRED (PRODUCT APPROVAL INCLUDES CALCS FOR 37X43 |
| | ROOF HATCH, ATTACHED TO 1/4" STEEL L ANGLE (4X4X1/4) |
| | ATTACHED TO STEEL JOISTS USING 8 3" FILLET WELDS, HATCH |
| | BOLTED TO THE LANGLE FRAME WITH 5/8" THROUGH BOLTS AS |
| | SPECIFIED IN THE PRODUCT APPROVAL). CONFIRM CONSISTENCY |
| | OF THE PRODUCT INSTALLED WITH THE PRODUCT APPROVAL |
| | (SIZE, INSTALLATION INSTRUCTIONS). |
| | |
| | 9. A ZONING REVIEW IS REQUIRED FOR ALL IMPROVEMENTS |
| | OUTSIDE OF THE BUILDING. PER ERIC SCHNEIDER, PLEASE |
| | INCORPORATE THIS WALKWAY AND STAIR INTO THE SITE PLAN |
| | FOR REVIEW. |
| | |