Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop P
Sequence Number 2
Notes
Date Text
2006-06-30 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 FROM PREVIOUS REVIEW. COMMENT NUMBER
 SHALL REMAIN THE SAME FOR CLARITY:
  
 4. SHT A-01 WATER CLOSETS REQUIRED PER
 TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR
 BUSINESS. SECTION 403.3 STATES THE
 REQUIRED WATER CLOSETS, LAVATORIES, ETC.
 SHALL BE DISTRIBUTED EVENLY BETWEEN THE
 SEXES. FLOOR PLAN INDICATES ONE WATER
 CLOSET IN THE WOMEN'S TOILET ROOM AND
 ONE WATER CLOSET AND TWO URINALS IN THE
 MEN'S TOILET ROOM. PLEASE CLARIFY.
 ***RESPONSE NOTED, BUT DRINKING FOUNTAIN
 ADDED TO THE FACTORY AREA ON THE MAIN
 FLOOR HAS NOT BEEN FOUND. PLEASE
 CLARIFY.
  
 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE
 AND TURNING AREA IN BOTH TOILET ROOMS
 AND FOR ALL ACCESSIBLE FIXTURES IN BOTH
 TOILET ROOMS.
 ***RESPONSE NOTED, BUT THE CLEAR FLOOR
 SPACE FOR THE WATER CLOSETS, URINAL AND
 SHOWERS ARE NOT SHOWN. - TURNING AREA
 SHALL BE LOCATED IN THE TOILET ROOM, NOT
 THE STALL.
  
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 ***RESPONSE NOTED, BUT THE EMERGENCY
 OVERFLOW SCUPPERS ARE REQUIRED PER
 SECTION 1107.1. PLEASE SIZE SCUPPERS PER
 SECTIONS AND TABLE REFERENCED ABOVE AND
 SHOW THE LOCATION OF ALL SCUPPERS. ALSO
 SEE SECTION 1503.4.3. SUBMIT A DETAIL
 FOR EMERGENCY OVER FLOW SCUPPERS. SHOW
 SCUPPERS ON EXTERIOR ELEVATIONS FOR
 BUILDING.
  
 11. SHT A-18 THE FOLLOWING SHALL BE
 SHOWN ON THE TOILET ROOMS ELEVATIONS:
 FOR W/C'S:
 A. 11-4.16.2 CLEAR FLOOR SPACE (NOT
 SHOWN).
 B. 11-4.16.5 FLUSH CONTROLS (MEN'S OK -
 WOMEN'S NOT CORRECT).
 FOR LAVS:
 A. 11-4.19.3 CLEAR FLOOR SPACE (NOT
 SHOWN)
 B. 11-4.19.5 FAUCETS (NO RESPONSE)
 FOR URINALS:
 B. 11-4.18.3 CLEAR FLOOR SPACE (NOT
 SHOWN).
 C. 11-4.18.4 FLUSH CONTROLS (NOT
 SHOWN).
 FOR SHOWERS
 B. 11-4.21.3 SEAT (IF INSTALLED) NOT
 SHOWN).
 E. 11-4.21.6 SHOWER UNIT (NOT SHOWN).
 F. 11-4.21.7 CURBS (NOT ADDRESSED)
 ***SUBMIT ALL ELEVATIONS FOR SHOWER.
  
 13. PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR
 POSSIBLE INTERCEPTORS AND/OR NUTRALIZER
 TANKS. CONTACT HER AT (561) 822-2271,
 (561) 822-2279 (FAX), OR [email protected] (E-MAIL).
 ***RESPONSE NOTED, WAITING FOR A
 RESPONSE FROM LYNN.
  
 15. SHT P-07 DETAIL 2 WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC
 "UNIONS" NOT APPROVED FOR
 WATER USAGE. PLEASE CHANGE TO
 "COUPLINGS".
 ***RESPONSE NOTED, BUT THE THERMAL
 EXPANSION CONTROL WAS NOT ADDRESSED.
  
 16. SHT P-08 WATER ISOMETRIC FOR THE
 MAIN LEVEL DOES NOT REFLECT THE PIPING
 SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE
 CORRELATE ISOMETRIC AND FLOW SCHEMATIC.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT THE RISER DIAGRAM
 STILL DOES NOT REFLECT THE FLOOR PLAN.
 AN EXTRA URINAL IS SHOWN, W/C MISSING,
 AND THE WATER PIPING CAN NOT BE
 INSTALLED AS SHOWN. (SEE EXAMPLE ON SHT
 P-09. IF OVERHEAD SHOW ALL DROPS.
  
 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS, NOR
 DOES IT REFLECT THE FLOOR PLAN SHT P-02.
 TRAPS ARE REQUIRED ON ALL FIXTURES
 EXCEPT THE CLEANOUTS AND THE WATER
 CLOSETS AS THE W/C'S HAVE AN INTEGRAL
 TRAP IN THE FIXTURES. SECTION 1002.1. -
 NO HORIZONTAL DRY VENTS PER SECTIONS
 905.3 & 905.4. - PIPING DOES NOT REFLECT
 THE FLOOR PLAN AT ESEW. NO PIPING SHOWN
 ON THE FLOOR PLAN. SHOW ALL PIPE SIZES
 ON ISOMETRIC. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
 ***RESPONSE NOTED, BUT RISER DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. 1 FLOOR DRAIN AND ONE
 4" VTR IS MISSING, AND THERE ARE
 NUMEROUS HORIZONTAL DRY VENTS STILL
 SHOWN. (SEE EXAMPLE IN RED ON SHEET FOR SOLUTION).
  
 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS. TRAPS
 ARE REQUIRED ON ALL FIXTURES EXCEPT
 CLEANOUTS AND WATER CLOSETS AS THE W/C'S
 HAVE INTEGRAL TRAPS IN THE FIXTURES. -
 DRY HORIZONTAL VENTS ARE NOT APPROVED
 PER SECTIONS 905.3 & 905.4.- MANY
 FIXTURES ARE NOT VENTED PROPERLY AS
 REQUIRED IN SECTION 901.2.1. (SEE
 EXAMPLE ON THIS SHEET ONE SET OF PLANS)
 - SHOW ALL PIPE SIZES ON THE ISOMETRICS. ***RESPONSE
 NOTED, BUT HORIZONTAL DRY
 VENTS STILL SHOWN. SOME PIPE SIZES NOT
 SHOWN.
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT SOME SECTION DO
 NOT INDICATE THE LENGHTS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ***RESPONSE
 NOTED, BUT INDICATE IF ALL
 PIPE IS WELDED. (NATURAL GAS PIPE NOT
 INDICATED). WELDING CERTIFICATE AND
 WELDING PROCEDURE REQUIRED AT TIME OF APPLICATION.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 ***RESPONSE NOTED, BUT THE TABLE USED
 FOR SIZING THE PIPE SHALL BE SUBMITTED
 WITH PLANS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***RESPONSE NOTED, BUT TOTAL DEVELOPED
 LENGTH IS NOT SHOWN, AND CAN NOT BE
 VERIFIED UNTIL ALL CUT SECTION
 MEASUREMENTS ARE SHOWN.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***NO RESPONSE TO THIS COMMENT FOUND.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ***NO RESPONSE NOTED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
  
 21. SHTS IR-1 THRU IR-5 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 THEN PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE DESIGN PROFESSIONAL.
 SECTION 106.1.1.
 ***RESPONSE NOTED, BUT TITLE BLOCKS
 SHALL BE REMOVED IF THE DESIGN
 PROFESSIONAL DID NOT DESIGN THE SYSTEM.
 THE PERSON WHO DESIGNED THE SYSTEM MUST
 PRINT HIS/HER NAME AND PLACE HIS/HER
 SIGNATURE ON EACH SHEET. SECTIONS
 106.1.2 AND 106.1.3.
  
 **************NEW COMMENTS**************
  
 1B. THE ACCESSIBLE STALLS IN THE TOILET
 ROOMS ARE NOT LARGE ENOUGH. MINIMUM SIZE
 FOR A AN ACCESSIBLE STALL IS 7'1". ONE
 STALL IS 6'0" AND THE OTHER IS 5'6". SEE
 ATTACHED SHEET FOR NEW CONSTRUCTION
 TOILET STALL FIGURE 30E.
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
  
 3B. FOR THE GAS SYSTEM: SLEEVES ARE
 REQUIRED WHERE THE GAS ENTERS THE
 BUILDING. SECTION 404.7.
  
 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW
 THE PIPING TO FU101 & FU201. SHOW SHUT
 OFF VALVES AND DRIP LINES FOR ALL UNITS.
 SECTIONS 408.2, 408.4, 409.4 & 409.5.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]