| Date |
Text |
| 2006-06-30 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | FROM PREVIOUS REVIEW. COMMENT NUMBER |
| | SHALL REMAIN THE SAME FOR CLARITY: |
| | |
| | 4. SHT A-01 WATER CLOSETS REQUIRED PER |
| | TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR |
| | BUSINESS. SECTION 403.3 STATES THE |
| | REQUIRED WATER CLOSETS, LAVATORIES, ETC. |
| | SHALL BE DISTRIBUTED EVENLY BETWEEN THE |
| | SEXES. FLOOR PLAN INDICATES ONE WATER |
| | CLOSET IN THE WOMEN'S TOILET ROOM AND |
| | ONE WATER CLOSET AND TWO URINALS IN THE |
| | MEN'S TOILET ROOM. PLEASE CLARIFY. |
| | ***RESPONSE NOTED, BUT DRINKING FOUNTAIN |
| | ADDED TO THE FACTORY AREA ON THE MAIN |
| | FLOOR HAS NOT BEEN FOUND. PLEASE |
| | CLARIFY. |
| | |
| | 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE |
| | AND TURNING AREA IN BOTH TOILET ROOMS |
| | AND FOR ALL ACCESSIBLE FIXTURES IN BOTH |
| | TOILET ROOMS. |
| | ***RESPONSE NOTED, BUT THE CLEAR FLOOR |
| | SPACE FOR THE WATER CLOSETS, URINAL AND |
| | SHOWERS ARE NOT SHOWN. - TURNING AREA |
| | SHALL BE LOCATED IN THE TOILET ROOM, NOT |
| | THE STALL. |
| | |
| | 9. SHT A-10 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE BEING DRAINED BY EACH |
| | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS IN |
| | CALCULATIONS. - SHOW THE LOCATION OF ALL |
| | OVERFLOW SCUPPERS, AND SIZE OF O/F |
| | SCUPPERS PER SECTIONS 1101.7, 1107.3 AND |
| | TABLE 1106.7. THE SIZING OF THE SCUPPERS |
| | CAN NOT BE DETERMINED WITHOUT REFERENCE |
| | TO THE DEFLECTION OF THE ROOF. PLEASE |
| | SHOW O/F SCUPPER CALCULATION ON PLANS |
| | INDICATING SIZE OF SCUPPERS AND PROVIDE |
| | DETAIL OF O/F SCUPPERS SHOWING HEIGHT |
| | AND WIDTH. |
| | ***RESPONSE NOTED, BUT THE EMERGENCY |
| | OVERFLOW SCUPPERS ARE REQUIRED PER |
| | SECTION 1107.1. PLEASE SIZE SCUPPERS PER |
| | SECTIONS AND TABLE REFERENCED ABOVE AND |
| | SHOW THE LOCATION OF ALL SCUPPERS. ALSO |
| | SEE SECTION 1503.4.3. SUBMIT A DETAIL |
| | FOR EMERGENCY OVER FLOW SCUPPERS. SHOW |
| | SCUPPERS ON EXTERIOR ELEVATIONS FOR |
| | BUILDING. |
| | |
| | 11. SHT A-18 THE FOLLOWING SHALL BE |
| | SHOWN ON THE TOILET ROOMS ELEVATIONS: |
| | FOR W/C'S: |
| | A. 11-4.16.2 CLEAR FLOOR SPACE (NOT |
| | SHOWN). |
| | B. 11-4.16.5 FLUSH CONTROLS (MEN'S OK - |
| | WOMEN'S NOT CORRECT). |
| | FOR LAVS: |
| | A. 11-4.19.3 CLEAR FLOOR SPACE (NOT |
| | SHOWN) |
| | B. 11-4.19.5 FAUCETS (NO RESPONSE) |
| | FOR URINALS: |
| | B. 11-4.18.3 CLEAR FLOOR SPACE (NOT |
| | SHOWN). |
| | C. 11-4.18.4 FLUSH CONTROLS (NOT |
| | SHOWN). |
| | FOR SHOWERS |
| | B. 11-4.21.3 SEAT (IF INSTALLED) NOT |
| | SHOWN). |
| | E. 11-4.21.6 SHOWER UNIT (NOT SHOWN). |
| | F. 11-4.21.7 CURBS (NOT ADDRESSED) |
| | ***SUBMIT ALL ELEVATIONS FOR SHOWER. |
| | |
| | 13. PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR |
| | POSSIBLE INTERCEPTORS AND/OR NUTRALIZER |
| | TANKS. CONTACT HER AT (561) 822-2271, |
| | (561) 822-2279 (FAX), OR [email protected] (E-MAIL). |
| | ***RESPONSE NOTED, WAITING FOR A |
| | RESPONSE FROM LYNN. |
| | |
| | 15. SHT P-07 DETAIL 2 WATER HEATER, |
| | THERMAL EXPANSION CONTROL REQUIRED PER |
| | SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC |
| | "UNIONS" NOT APPROVED FOR |
| | WATER USAGE. PLEASE CHANGE TO |
| | "COUPLINGS". |
| | ***RESPONSE NOTED, BUT THE THERMAL |
| | EXPANSION CONTROL WAS NOT ADDRESSED. |
| | |
| | 16. SHT P-08 WATER ISOMETRIC FOR THE |
| | MAIN LEVEL DOES NOT REFLECT THE PIPING |
| | SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE |
| | CORRELATE ISOMETRIC AND FLOW SCHEMATIC. |
| | SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT THE RISER DIAGRAM |
| | STILL DOES NOT REFLECT THE FLOOR PLAN. |
| | AN EXTRA URINAL IS SHOWN, W/C MISSING, |
| | AND THE WATER PIPING CAN NOT BE |
| | INSTALLED AS SHOWN. (SEE EXAMPLE ON SHT |
| | P-09. IF OVERHEAD SHOW ALL DROPS. |
| | |
| | 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC |
| | DOES NOT MEET CODE REQUIREMENTS, NOR |
| | DOES IT REFLECT THE FLOOR PLAN SHT P-02. |
| | TRAPS ARE REQUIRED ON ALL FIXTURES |
| | EXCEPT THE CLEANOUTS AND THE WATER |
| | CLOSETS AS THE W/C'S HAVE AN INTEGRAL |
| | TRAP IN THE FIXTURES. SECTION 1002.1. - |
| | NO HORIZONTAL DRY VENTS PER SECTIONS |
| | 905.3 & 905.4. - PIPING DOES NOT REFLECT |
| | THE FLOOR PLAN AT ESEW. NO PIPING SHOWN |
| | ON THE FLOOR PLAN. SHOW ALL PIPE SIZES |
| | ON ISOMETRIC. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT RISER DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET |
| | CODE REQUIREMENTS. 1 FLOOR DRAIN AND ONE |
| | 4" VTR IS MISSING, AND THERE ARE |
| | NUMEROUS HORIZONTAL DRY VENTS STILL |
| | SHOWN. (SEE EXAMPLE IN RED ON SHEET FOR SOLUTION). |
| | |
| | 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC |
| | DOES NOT MEET CODE REQUIREMENTS. TRAPS |
| | ARE REQUIRED ON ALL FIXTURES EXCEPT |
| | CLEANOUTS AND WATER CLOSETS AS THE W/C'S |
| | HAVE INTEGRAL TRAPS IN THE FIXTURES. - |
| | DRY HORIZONTAL VENTS ARE NOT APPROVED |
| | PER SECTIONS 905.3 & 905.4.- MANY |
| | FIXTURES ARE NOT VENTED PROPERLY AS |
| | REQUIRED IN SECTION 901.2.1. (SEE |
| | EXAMPLE ON THIS SHEET ONE SET OF PLANS) |
| | - SHOW ALL PIPE SIZES ON THE ISOMETRICS. ***RESPONSE |
| | NOTED, BUT HORIZONTAL DRY |
| | VENTS STILL SHOWN. SOME PIPE SIZES NOT |
| | SHOWN. |
| | |
| | 19. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | ***RESPONSE NOTED, BUT SOME SECTION DO |
| | NOT INDICATE THE LENGHTS. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. ***RESPONSE |
| | NOTED, BUT INDICATE IF ALL |
| | PIPE IS WELDED. (NATURAL GAS PIPE NOT |
| | INDICATED). WELDING CERTIFICATE AND |
| | WELDING PROCEDURE REQUIRED AT TIME OF APPLICATION. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - INDICATE ON PLANS TABLE |
| | BEING USED OF ALL GAS PIPING. |
| | ***RESPONSE NOTED, BUT THE TABLE USED |
| | FOR SIZING THE PIPE SHALL BE SUBMITTED |
| | WITH PLANS. |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ***RESPONSE NOTED, BUT TOTAL DEVELOPED |
| | LENGTH IS NOT SHOWN, AND CAN NOT BE |
| | VERIFIED UNTIL ALL CUT SECTION |
| | MEASUREMENTS ARE SHOWN. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ***NO RESPONSE TO THIS COMMENT FOUND. |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ***NO RESPONSE NOTED. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE NOTED. |
| | |
| | 21. SHTS IR-1 THRU IR-5 IF THE DESIGN |
| | PROFESSIONAL IS AN ARCHITECT OR ENGINEER |
| | THEN PLANS SHALL BE SIGNED, SEALED, AND |
| | DATED BY THE DESIGN PROFESSIONAL. |
| | SECTION 106.1.1. |
| | ***RESPONSE NOTED, BUT TITLE BLOCKS |
| | SHALL BE REMOVED IF THE DESIGN |
| | PROFESSIONAL DID NOT DESIGN THE SYSTEM. |
| | THE PERSON WHO DESIGNED THE SYSTEM MUST |
| | PRINT HIS/HER NAME AND PLACE HIS/HER |
| | SIGNATURE ON EACH SHEET. SECTIONS |
| | 106.1.2 AND 106.1.3. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 1B. THE ACCESSIBLE STALLS IN THE TOILET |
| | ROOMS ARE NOT LARGE ENOUGH. MINIMUM SIZE |
| | FOR A AN ACCESSIBLE STALL IS 7'1". ONE |
| | STALL IS 6'0" AND THE OTHER IS 5'6". SEE |
| | ATTACHED SHEET FOR NEW CONSTRUCTION |
| | TOILET STALL FIGURE 30E. |
| | |
| | 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS |
| | FOR THE REGULATORS USED. |
| | INDICATE IF THE REGULATOR WILL BE VENTED |
| | AND IF SO INDICATE THE MATERIAL USED FOR |
| | THE VENT. ALSO SHOW VENTING ROUTE FOR |
| | REGULATOR. SECTION 106.1.1. |
| | |
| | 3B. FOR THE GAS SYSTEM: SLEEVES ARE |
| | REQUIRED WHERE THE GAS ENTERS THE |
| | BUILDING. SECTION 404.7. |
| | |
| | 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW |
| | THE PIPING TO FU101 & FU201. SHOW SHUT |
| | OFF VALVES AND DRIP LINES FOR ALL UNITS. |
| | SECTIONS 408.2, 408.4, 409.4 & 409.5. |
| | |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |