Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop G
Sequence Number 2
Notes
Date Text
2007-03-09 07:42:42DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR
 THE INDUSTRIAL FURNACE/DRYER IS REQUIRED SHOWING THE
 LISTING AND BTU LOAD.
  
 21. OK
  
 **************NEW COMMENTS**************
  
 1B. OK
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. SPECIFICATIONS
 FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT THE MANUF. SPECIFICATION
 SHEETS FOR THE REGULATORS ARE REQUIRED. PLEASE INDICATE
 MODEL NUMBER BEING USED FOR EACH REGULATOR.
  
 3B. OK
 4B. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]