Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-08-08 00:00:00***DENIED***
  
 PLEASE SEE LAST FIRE REVIEW AND PROVIDE
 ALL NECESSARY RESPONSES.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
 PLEASE SEE SOME COMMENTS FROM FIRST FIRE
 REVIEW AND NEW COMMENTS:
  
 COMMENT
 1) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO SHT A-01 CODE SUMMARY.
  
 2) PLEASE ADD NFPA STANDARDS WITH
 ADOPTED ADDITIONS TO SHT A-01 CODE
 SUMMARY.
  
 3) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO PLANS.
  
 4) PLEASE ADD NFPA STANDARD WITH ADOPTED
 EDITION TO PLANS.
  
 5) OK
  
 6) OK
  
 7) OK
  
 NEW COMMENTS
  
 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE FOR ALL NEW
 BUILDINGS PROTECTED BY AN AUTOMATIC FIRE
 SPRINKLER SYSTEM. M-07 NOTE (7) IS NOT
 THE SAME.
  
 9) MSDS SHEETS REQUIRED IN APPROVED
 LOCATION AT FACILITY.
  
 10) ACCESS FOR EMERGENCY VEHICLES AND
 WATER SUPPLY TO COMPLY WITH NFPA 1, 2003
 EDITION.
  
 11) MANUFACTURER SPEC SHEETS REQUIRED
 FOR GENERATOR AND FUEL EQUIPMENT.
  
 12) ADDRESS REQUIRED ON BUILDING THAT
 SHALL BE A MINIMUM OF 6" IN HEIGHT AND
 CONTRASTING TO THE BACKGROUND.
  
 13) PLEASE CLEARLY IDENTIFY THE
 LOCATIONS OF NEW AND EXISTING FIRE
 HYDRANTS ON CIVIL PLANS.
  
 14) PLEASE PROVIDE ADDITION INFORMATION
 AND SPEC SHEETS FOR ACCESS GATES. PLEASE
 INDICATE FAILSAFE MEASURES IN THE EVENT
 OF POWER FAILURE.
  
 15) SHT M-07 INDICATES FIRE PROTECTION
 PLAN, BUT DOES NOT SHOW FIRE SPRINKLER
 LAYOUT. THAT INFORMATION SHALL BE
 INCLUDED IN ACCORDANCE WITH FBC.
  
 16) SOME RATED DOORS ARE CALLED OUT ON
 DOOR SCHEDULE, HOWEVER NO MENTION OF UL
 LISTED CLOSERS AS DOORS ARE REQUIRED TO
 POSITIVELY LATCH.
  
 17) ALL REQUIRED HAZARDOUS MATERIAL
 IDENTIFICATION SHALL BE DISPLAYED IN
 ACCORDANCE WITH NFPA 704.
  
 18) DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 19) EXIT SIGNS ARE DISPLAYED AT EXIT
 DOORS, HOWEVER IT WOULD APPEAR THAT MORE
 EXIT SIGNS MAY BE REQUIRED TO ILLUSTRATE
 OBVIOUS TRAVEL DIRECTION WITHIN AREAS OF
 THE MEANS OF EGRESS.
  
 20) A KNOX BOX WILL BE REQUIRED FOR THE
 BUILDING. APPLICATIONS CAN BE OBTAINED
 AT THE BUREAU OF FIRE PREVENTION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  