| 2006-08-08 00:00:00 | ***DENIED*** |
| | |
| | PLEASE SEE LAST FIRE REVIEW AND PROVIDE |
| | ALL NECESSARY RESPONSES. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | PLEASE SEE SOME COMMENTS FROM FIRST FIRE |
| | REVIEW AND NEW COMMENTS: |
| | |
| | COMMENT |
| | 1) PLEASE ADD NFPA STANDARD WITH ADOPTED |
| | EDITION TO SHT A-01 CODE SUMMARY. |
| | |
| | 2) PLEASE ADD NFPA STANDARDS WITH |
| | ADOPTED ADDITIONS TO SHT A-01 CODE |
| | SUMMARY. |
| | |
| | 3) PLEASE ADD NFPA STANDARD WITH ADOPTED |
| | EDITION TO PLANS. |
| | |
| | 4) PLEASE ADD NFPA STANDARD WITH ADOPTED |
| | EDITION TO PLANS. |
| | |
| | 5) OK |
| | |
| | 6) OK |
| | |
| | 7) OK |
| | |
| | NEW COMMENTS |
| | |
| | 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE FOR ALL NEW |
| | BUILDINGS PROTECTED BY AN AUTOMATIC FIRE |
| | SPRINKLER SYSTEM. M-07 NOTE (7) IS NOT |
| | THE SAME. |
| | |
| | 9) MSDS SHEETS REQUIRED IN APPROVED |
| | LOCATION AT FACILITY. |
| | |
| | 10) ACCESS FOR EMERGENCY VEHICLES AND |
| | WATER SUPPLY TO COMPLY WITH NFPA 1, 2003 |
| | EDITION. |
| | |
| | 11) MANUFACTURER SPEC SHEETS REQUIRED |
| | FOR GENERATOR AND FUEL EQUIPMENT. |
| | |
| | 12) ADDRESS REQUIRED ON BUILDING THAT |
| | SHALL BE A MINIMUM OF 6" IN HEIGHT AND |
| | CONTRASTING TO THE BACKGROUND. |
| | |
| | 13) PLEASE CLEARLY IDENTIFY THE |
| | LOCATIONS OF NEW AND EXISTING FIRE |
| | HYDRANTS ON CIVIL PLANS. |
| | |
| | 14) PLEASE PROVIDE ADDITION INFORMATION |
| | AND SPEC SHEETS FOR ACCESS GATES. PLEASE |
| | INDICATE FAILSAFE MEASURES IN THE EVENT |
| | OF POWER FAILURE. |
| | |
| | 15) SHT M-07 INDICATES FIRE PROTECTION |
| | PLAN, BUT DOES NOT SHOW FIRE SPRINKLER |
| | LAYOUT. THAT INFORMATION SHALL BE |
| | INCLUDED IN ACCORDANCE WITH FBC. |
| | |
| | 16) SOME RATED DOORS ARE CALLED OUT ON |
| | DOOR SCHEDULE, HOWEVER NO MENTION OF UL |
| | LISTED CLOSERS AS DOORS ARE REQUIRED TO |
| | POSITIVELY LATCH. |
| | |
| | 17) ALL REQUIRED HAZARDOUS MATERIAL |
| | IDENTIFICATION SHALL BE DISPLAYED IN |
| | ACCORDANCE WITH NFPA 704. |
| | |
| | 18) DUCT SMOKE DETECTORS SHALL INITIATE |
| | A GENERAL FIRE ALARM IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 19) EXIT SIGNS ARE DISPLAYED AT EXIT |
| | DOORS, HOWEVER IT WOULD APPEAR THAT MORE |
| | EXIT SIGNS MAY BE REQUIRED TO ILLUSTRATE |
| | OBVIOUS TRAVEL DIRECTION WITHIN AREAS OF |
| | THE MEANS OF EGRESS. |
| | |
| | 20) A KNOX BOX WILL BE REQUIRED FOR THE |
| | BUILDING. APPLICATIONS CAN BE OBTAINED |
| | AT THE BUREAU OF FIRE PREVENTION. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |