| Date |
Text |
| 2006-06-20 00:00:00 | 1) THE LOAD CALCULATIONS SHOWN ON |
| | DRAWINGS ARE STILL VERY VAGUE.YOU |
| | INDICATE AN 80% DIVERSITY?IN ARTICLE |
| | 430 FOR FEEDERS THERE IS NO 80% |
| | DIVERSITY THAT I CAN FIND, PLEASE |
| | INDICATE WHICH SECTION APPLIES. SHOW HOW |
| | LOADS WHERE CALCULATED FOR SERVICE |
| | ENTRANCE. DESCRIBE OTHER LOADS, PER |
| | ARTICLE 220 |
| | |
| | 2) THE MAIN SWITCH GEAR ROOM IS ON THE |
| | MEZZ.LEVEL MAINS SHALL BE READILY |
| | ACCESSIBLE.THE SHUNT TRIPS ARE OK BUT |
| | YOU STILL HAVE TO HAVE READILY |
| | ACCESSIBLE MAINS WHICH ARE 50' UP OF THE |
| | GROUND.230.70 A1, A3 |
| | |
| | 3) THE SERVICE ENTRANCE CONDUCTORS ARE |
| | NOT ALLOWED TO TRAVEL THROUGH THE |
| | BUILDING. NO MORE THAN 8' OF CONDUCTOR |
| | IS ALLOWED IN THE BUILDING. |
| | |
| | 4) CUT SHEETS FOR THE CRUSHER, SCREENER |
| | ARE THESE TOTALY ENCLOSED??????? |
| | |
| | 5) LIGHTING CONTROL IS TO BE DONE PER |
| | FBC CHAPTER 13 SECTION 415. |
| | |
| | 6) GENERATOR MAIN IS TO BE INSTALLED PER |
| | 700.12 B(6). |
| | |
| | 7) IF A DUST COLECTOR IS NEEDED FOR THE |
| | SILOS, WHAT HAPPENS IF IT DOES NOT WORK? |
| | |
| | 8) ON PAGE E-14 THERE IS A JUNCTION BOX |
| | ON THE OUTSIDE WALL, IT HAS FPL AND BELL |
| | SOUTH INSTALLEDIN IT????????????? |
| | |
| | 9) THE AREAS AROUND THE SCREENER AND |
| | CRUSHER ARE STILL IN QUESTION AS A |
| | CLASSIFIED AREA. IF EQUIPMENT IS NOT |
| | TOTALY ENCLOSED THEY SHALL BE CLASSIFIED |
| | AS A CLASS II AREA. PLEASE SHOW THE |
| | EXTENT OF THE CLASSIFIED AREA. |
| | |
| | 10) SIGNATURE ON THE DRAWINGS IS A STAMP |
| | AND NOT A SIGNED SIGNATURE, THIS OFFICE |
| | MAY RETAIN A COPY OF THESE DRAWING TO |
| | SEND TO THE STATE FOR NON-COMPLIANCE |
| | WITH THE FLORIDA STATUTES. |