2006-06-20 00:00:001) THE LOAD CALCULATIONS SHOWN ON
 DRAWINGS ARE STILL VERY VAGUE.YOU
 INDICATE AN 80% DIVERSITY?IN ARTICLE
 430 FOR FEEDERS THERE IS NO 80%
 DIVERSITY THAT I CAN FIND, PLEASE
 INDICATE WHICH SECTION APPLIES. SHOW HOW
 LOADS WHERE CALCULATED FOR SERVICE
 ENTRANCE. DESCRIBE OTHER LOADS, PER
 ARTICLE 220
  
 2) THE MAIN SWITCH GEAR ROOM IS ON THE
 MEZZ.LEVEL MAINS SHALL BE READILY
 ACCESSIBLE.THE SHUNT TRIPS ARE OK BUT
 YOU STILL HAVE TO HAVE READILY
 ACCESSIBLE MAINS WHICH ARE 50' UP OF THE
 GROUND.230.70 A1, A3
  
 3) THE SERVICE ENTRANCE CONDUCTORS ARE
 NOT ALLOWED TO TRAVEL THROUGH THE
 BUILDING. NO MORE THAN 8' OF CONDUCTOR
 IS ALLOWED IN THE BUILDING.
  
 4) CUT SHEETS FOR THE CRUSHER, SCREENER
 ARE THESE TOTALY ENCLOSED???????
  
 5) LIGHTING CONTROL IS TO BE DONE PER
 FBC CHAPTER 13 SECTION 415.
  
 6) GENERATOR MAIN IS TO BE INSTALLED PER
 700.12 B(6).
  
 7) IF A DUST COLECTOR IS NEEDED FOR THE
 SILOS, WHAT HAPPENS IF IT DOES NOT WORK?
  
 8) ON PAGE E-14 THERE IS A JUNCTION BOX
 ON THE OUTSIDE WALL, IT HAS FPL AND BELL
 SOUTH INSTALLEDIN IT?????????????
  
 9) THE AREAS AROUND THE SCREENER AND
 CRUSHER ARE STILL IN QUESTION AS A
 CLASSIFIED AREA. IF EQUIPMENT IS NOT
 TOTALY ENCLOSED THEY SHALL BE CLASSIFIED
 AS A CLASS II AREA. PLEASE SHOW THE
 EXTENT OF THE CLASSIFIED AREA.
  
 10) SIGNATURE ON THE DRAWINGS IS A STAMP
 AND NOT A SIGNED SIGNATURE, THIS OFFICE
 MAY RETAIN A COPY OF THESE DRAWING TO
 SEND TO THE STATE FOR NON-COMPLIANCE
 WITH THE FLORIDA STATUTES.