| 2008-09-04 18:51:40 | ****CORRECTIONS**** |
| | ****REVISION, VARIOUS SHEETS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. COMMENT FROM BUILDING REVIEW 13, DOORS 214.2 AND |
| | 219.1 AT STAIR #1 ARE TO BE FIRE RESISTANCE RATED AS |
| | THEY ARE BOTH LOCATED IN A 2 HOUR WALL, FBC715.3. |
| | |
| | 2. SHEET A5, MANY WALL TYPES CHANGED FROM THE RECORD |
| | SET BUT ARE NOT CLOUDED AS CHANGES. PLEASE CHECK THE |
| | ENTIRE SHEET FOR CHANGES, AND CLOUD AND NUMBER THOSE |
| | REVISIONS. OLD REVISIONS (BEFORE REVISION 5) DO NOT |
| | NEED TO BE CLOUDED AS THEY ARE NOW A PART OF THE RECORD |
| | SET. |
| | |
| | 3. SHEET A5 DOES NOT MATCH THE LIFE SAFETY PLAN. THE |
| | RECORD SET HAS A STATEMENT THAT ONLY ONE EXIT IS |
| | REQUIRED FROM THE SECOND FLOOR. AFTER FURTHER |
| | INVESTIGATION, I HAVE DISCOVERED THAT THIS STATEMENT IS |
| | NOT CORRECT, THEREFORE THE LIFE SAFETY PLAN IN OUR |
| | RECORD SET IS NOT CODE COMPLIANT. THE NEW ARCHITECT OF |
| | RECORD AGREED TO CORRECT THIS ERROR. ALTHOUGH WE HAD |
| | THESE DISCUSSIONS IN FEBRUARY, THAT SHEET HAS STILL NOT |
| | BEEN REVISED. PLEASE SUBMIT. ALSO REVISE ANY OTHER |
| | SHEETS AFFECTED BY THE CHANGE TO SHEET A5. |
| | |
| | |
| | |
| | |