2008-08-18 14:10:46****CORRECTIONS****
 ***SUBMITTAL 15890-002B***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SOUTH FLORIDA BUILDING CODE IS REFERENCED; THIS IS
 NOT GOVERNING CODE.ANCHORING SHOULD BE SPECIFIC AS TO
 BRAND AND ANCHOR."TO CODE" IS NOT A SPECIFICATION;
 THE CODE DOES NOT INCLUDE PRESCRIPTIVE METHOD OF CURB
 ATTACHMENT.
  
 2.STRUCTURAL ENGINEER HAS REQUIRED THAT OPENINGS BE
 EVALUATED BY THE PRECASTER SPECIALTY (DELEGATED)
 ENGINEER.PLEASE HAVE THIS SUBMITTAL REVIEWED BY THE
 SPECIALTY ENGINEER AS WELL AS THE ENGINEER OF RECORD
 FOR THE STRUCTURE.REVISE STRUCTURAL DRAWINGS AS
 NECESSARY.
  
 3.AN OPENING IS SHOWN IN STAIR 1.SEE FBC1019.1.1,
 OPENINGS IN VERTICAL EXIT ENCLOSURES NOT PERMITTED
 EXCEPT AS NOTED.PLEASE CLARIFY PURPOSE; HAVE REVIEWED
 BY DESIGNER OF RECORD FOR LIFE SAFETY ISSUE.
  
 4.THE SHOP DRAWING REVIEW STAMP AND THE SUBMITTAL ARE
 NOT ENTIRELY LEGIBLE.PLEASE PROVIDE THREE LEGIBLE
 SETS.
  