2008-05-05 14:10:48****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE SHEET S1.THE ROOF COVER IS TO MEET THE
 MINIMUMS SPECIFIED BY THE ENGINEER WHO DESIGNED THE
 BUILDING; IN THIS CASE, -53.33, -89.48, -134.67 FOR
 ZONES 1, 2, AND 3 RESPECTIVELY.EITHER REVISE THE
 ROOFING SUBMITTAL TO COMPLY WITH DESIGN CRITERIA ON S1
 OR REVISE SHEET S1.THE FORM SUBMITTED (HVHZ UNIFORM
 PERMIT APPLICATION FORM) MUST CORRELATE WITH THE PLANS
 IF SUBMITTED.THIS FORM NOW SSPECIFIES DESIGN
 PRESSURES AS -40.6, -73.3, AND -73.1.
  
 2.IF SHEET S1 IS REVISED TO THE PRESSURES SPECIFIED
 ON THE HVHZ FORM (-73.3 FOR ZONES 2 AND 3), PLEASE
 PROVIDE CALCULATIONS.SEE TABLES FBC1609.6.2.1(2) AND
 (4).IF THIS IS EXPOSURE C, 48 FEET, THE DESIGN
 PRESSURE FOR ZONE 2 USING THE TABLE WOULD BE
 APPROXIMATELY -90.58.WHEN DESIGN PRESSURES ARE
 SIGNIFICANTLY LOWER THAN TABLE, SIGNED AND SEALED
 CALCULATIONS ARE REQUIRED.
  
 3.THE HVHZ APPLICATION SHOWS A 3' PARAPET.SEE
 SHEET A 001 AND OTHER SHEETS; THE PLAN DOES APPEAR TO
 SHOW A 3' CONTINUOUS PARAPET WALL.WHEN RESUBMITTING,
 IF USING ZONE 2 PRESSURES FOR ZONE 3, PLEASE ADVISE AS
 TO WHERE THIS CAN BE LOCATED ON THE PLAN.
  
  
  
  
  