| 2008-05-05 14:10:48 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.SEE SHEET S1.THE ROOF COVER IS TO MEET THE |
| | MINIMUMS SPECIFIED BY THE ENGINEER WHO DESIGNED THE |
| | BUILDING; IN THIS CASE, -53.33, -89.48, -134.67 FOR |
| | ZONES 1, 2, AND 3 RESPECTIVELY.EITHER REVISE THE |
| | ROOFING SUBMITTAL TO COMPLY WITH DESIGN CRITERIA ON S1 |
| | OR REVISE SHEET S1.THE FORM SUBMITTED (HVHZ UNIFORM |
| | PERMIT APPLICATION FORM) MUST CORRELATE WITH THE PLANS |
| | IF SUBMITTED.THIS FORM NOW SSPECIFIES DESIGN |
| | PRESSURES AS -40.6, -73.3, AND -73.1. |
| | |
| | 2.IF SHEET S1 IS REVISED TO THE PRESSURES SPECIFIED |
| | ON THE HVHZ FORM (-73.3 FOR ZONES 2 AND 3), PLEASE |
| | PROVIDE CALCULATIONS.SEE TABLES FBC1609.6.2.1(2) AND |
| | (4).IF THIS IS EXPOSURE C, 48 FEET, THE DESIGN |
| | PRESSURE FOR ZONE 2 USING THE TABLE WOULD BE |
| | APPROXIMATELY -90.58.WHEN DESIGN PRESSURES ARE |
| | SIGNIFICANTLY LOWER THAN TABLE, SIGNED AND SEALED |
| | CALCULATIONS ARE REQUIRED. |
| | |
| | 3.THE HVHZ APPLICATION SHOWS A 3' PARAPET.SEE |
| | SHEET A 001 AND OTHER SHEETS; THE PLAN DOES APPEAR TO |
| | SHOW A 3' CONTINUOUS PARAPET WALL.WHEN RESUBMITTING, |
| | IF USING ZONE 2 PRESSURES FOR ZONE 3, PLEASE ADVISE AS |
| | TO WHERE THIS CAN BE LOCATED ON THE PLAN. |
| | |
| | |
| | |
| | |
| | |