Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop B
Sequence Number 13
Notes
Date Text
2008-04-22 08:20:55****CORRECTIONS****
 ***REVISION, VARIOUS SHEETS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.A ROOF HATCH IS SHOWN ON S07; PLEASE PROVIDE STATE
 OR LOCAL PRODUCT APPROVAL FAC9B72.THIS MAY BE A
 PROVISO ITEM; HOWEVER, PLEASE BE ADVISED THAT THIS
 ISSUE HAS DELAYED (AND ALMOST PREVENTED) C.O. ON OTHER
 JOBS.TO MY KNOWLEDGE, NO MANUFACTURER HAS YET
 OBTAINED STATE PRODUCT APPROVAL FOR A ROOF HATCH, AND
 ONLY ONE HAS OBTAINED A LOCAL PRODUCT APPROVAL.THERE
 HAS BEEN A DECLARATORY STATEMENT ISSUED BY THE STATE
 CONFIRMING THAT ROOF HATCH FALLS UNDER FAC9B72.
  
 2.SECTION 4 S05, DETAIL INDICATOR 4 S14 IS NO LONGER
 INCORPORATED IN THE DETAIL.IS THERE A NEW DETAIL FOR
 THIS, OR IS IT UNNECESSARY?
  
 3.SHEET S20 DOES NOT MATCH THE S20 WE HAVE ON FILE.
 THE SHEET S20 SUBMITTED IS TITLED SCRUBBER, COOLING
 TOWER & PELLET OIL TANK FOUNDATION PLANS & SECTIONS,
 BUT THE INDEX DOES NOT SHOW A SHEET WITH THIS TITLE IN
 THE ISSUED SET OF PLANS.IT APPEARS TO BE A NEW SHEET,
 AND SHOULD HAVE A UNIQUE SHEET NUMBER.THE SHEET ON
 FILE IS TITLED COOLING TOWER PAD & CHEMICAL STORAGE.
 DOES THE NEW SHEET REPLACE THIS ONE OR SHOULD IT BE
 ADDED?
  
 4. S20, COOLING TOWER FOUNDATION PLAN, SHOWS A CLOUD
 WITH A NOTE THAT STATES HOLD.PLEASE PROVIDE MORE
 INFORMATION.
  
 5. SEE SHEET A001A LIFE SAFETY PLAN OVERALL AND THE
 REVISED A001B.THE TRAVEL DISTANCE FROM STAIR 5 IS TO
 BE MEASURED ALONG THE NATURAL PATH OF TRAVEL.AS
 DRAWN, THE PATH APPEARS TO GO THROUGH EQUIPMENT.
 PLEASE REVISE. FBC1015.1.
  
 6.CLARIFY COMMON PATH OF TRAVEL, SHOWN AS 4FT.SEE
 DEFINITION, FBC1002.
  
 7.SEE PREVIOUS LIST; THE CERTIFICATE OF AUTHORIZATION
 FOR THE ARCHITECTURE FIRM AND NAME OF INDIVIDUAL
 SIGNING THE DOCUMENT IS TO BE PRINTED ON EACH SHEET,
 FAC61G16-23.002, 003.
  
 8.THE CERTIFICATE OF AUTHORIZATION FOR THE
 ENGINEERING FIRM IS TO BE PRINTED ON EACH SHEET,
 FAC6G15-23.002.
  
 9. A05, WALL TYPE B STATES THAT THIS IS 8IN CMU WITH
 6IN 20 GAGE METAL STUDS.WALL CONSTRUCTION IS NOT
 CLEAR, PLEASE REVISE OR PROVIDE A DETAIL.
  
 10. DOORS 214.2 AND 219.1 AT STAIR #1 ARE TO BE FIRE
 RESISTANCE RATED AS THEY ARE BOTH LOCATED IN A 2 HOUR
 WALL, FBC715.3.
  
 11. I WAS UNABLE TO LOCATE HARDWARE SET DESCRIPTIONS TO
 CONFIRM COMPLIANCE WITH FBC715.3.7.PLEASE ADVISE.
  
 12.EXITING FROM THE SECOND FLOOR DOES NOT COMPLY WITH
 MAXIMUM TRAVEL DISTANCE FOR ONE EXIT, SEE FBC TABLE
 1018.2.THE TRAVEL DISTANCE IS TO BE MEASURED FROM THE
 FARTHEST POINT TO THE EXIT DISCHARGE; IN THIS CASE, TO
 THE EXIT DOOR ON THE FIRST FLOOR.AS THE DISTANCE FROM
 THE TOP OF STAIR #5 TO THE EXIT DOOR EXCEEDS 124FT,
 THIS AREA HAS A TRAVEL DISTANCE GREATER THAN THE 75FT
 PERMITTED.
  