Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop B
Sequence Number 12
Notes
Date Text
2008-01-03 07:50:16****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ARCHITECT STATES ON SHEET A001B, "ONLY ONE EXIT IS
 REQUIRED FROM THE SECOND LEVEL."PLEASE CLARIFY THIS
 STATEMENT AND DESIGN, SEE FBC TABLE 1018.2.
  
 2.SEE FBC1013.2, EGRESS THROUGH INTERVENING SPACES.
 THIS IS NOT ALLOWED THROUGH KITCHENS, STORAGE, CLOSETS
 OR SIMILAR SPACES.EXITING FROM THE PROCESSING AREA
 THROUGH THE MECHANICAL ROOM APPEARS TO BE PROHIBITED BY
 THIS CODE SECTION.
  
 3.ALL INFORMATIION REQUIRED BY FAC61G1-15.23 IS
 REQUIRED FOR THE ARCHITECT.IF THE TITLE BLOCK FOR HDR
 ENGINEERING IS THE TITLE BLOCK FOR THE ARCHITECT,
 PROVIDE THE CERTIFICATE OF AUTHORIZATION (ARCHITECT
 BUSINESS) LICENSE NUMBER ON THE PLAN.
  