| Date |
Text |
| 2009-04-13 13:53:21 | REVISION DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | CITY WPB MUNICIPAL CODE |
| | |
| | 1. SHTS P-02 & P-10 SHOWS TWO SUMP PUMPS AT THE SILOS. |
| | PLEASE INDICATE WHAT WILL BE DRAINING INTO THE SUMPS. |
| | SECTION 106.1.2 (MORE INFORMATION REQUIRED). IF IT IS |
| | STORM WATER DRAINING INTO THE SUMP, THEN IT CAN NOT BE |
| | CONNECTED TO THE SANITARY SYSTEM PER ARTICLE III |
| | SECTION 90-125(5). IF ITS WASTE WATER THEN EXPLAINATION |
| | IS REQUIRED ON HOW TO KEEP THE STORM WATER FROM THE |
| | SUMP. IF THERE ARE CHEMICALS DRAINING INTO THE SUMPS, |
| | THEN A NEUTRALIZER TANK MAY BE REQUIRED AND THE UTILITY |
| | DEPT. INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE |
| | SHALL BE CONTACTED. (HOLLY MCGRATH LABORATORY |
| | SUPERVISOR - (561) 822-2271) PLEASE CLARIFY. |
| | |
| | 2. SHTS P-02 & P-10 THE SUMPS SHALL BE VENTED. PLEASE |
| | INDICATE HOW THIS WILL BE ACCOMPLISHED. THIS IS NOT |
| | SHOWN ON THE FLAT PLAN, NOR ON THE ISOMETRIC RISER |
| | DIAGRAM. SECTION 916.5. |
| | |
| | 3. SHT P-07 DETAIL 2 SHOWS THE DRIP LEG FOR THE GAS |
| | LINE EXTENDING TO A DRIP PAN. PLEASE CALRIFY. THE |
| | DRIP/SEDIMENT TRAP SHALL BE A CAPPED NIPPLE. AS |
| | INDICATED THIS NOT INDICATED. SECTION 408.4. |
| | |
| | 4. SHT P-07 DETAIL 4 SHOWS THE HOT WATER SUPPLY LINE |
| | DIRECTIONAL ARROW AGAINST THE FLOW TO THE TEMPERING |
| | VALVE. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 5. SHT P-08 MAIN LEVEL PLUMBING ISOMETRIC DOES NOT |
| | REFLECT THE CHANGES INDICATED ON SHEET P-01 NOR MANY |
| | OTHER WATER LINES IN THE SYSTEM. FOR EXAMPLE MANY |
| | BYPASSES, REDUCERS, LINES, THE 2" PWC TO MECH ROOM, THE |
| | 2" WM TO 2ND FLOOR OFFICE AREA, P1 ON LINES TO P303 & |
| | P304, SOLENOID VALVES & SHUT OFF VALVES TO BS 301 & BS |
| | 302. THESE ARE JUST SOME EXAMPLES. PLEASE CORRELATE THE |
| | ISOMETRIC RISER DIAGRAM WITH THE POTABLE & INDUSTRIAL |
| | WATER FLOW SCHEMATIC SO THE PLANS REFLECT EACH OTHER. |
| | SECTION 106.1.1 |
| | |
| | 6. SHT P-11 FD-3 AT THE TOP OF THE 4" RISER (SANITARY |
| | DOWN TO RECEIVING) IS NOT VENTED. SECTION 901.2.1. ALSO |
| | SHOW THE VENT TERMINATION FOR THE FD-3 FIXTURES AT THE |
| | END OF THE SAME STACK FOR THE FLOOR DRAINS. SECTION |
| | 903.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |