Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop P
Sequence Number 1
Notes
Date Text
2006-03-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 PLAN REVIEW ONLY
 1. PLANS INDICATED DOCUMENT 90% COMPLETE
 AND AS SUCH MORE COMMENTS MAY BE
 FORTHCOMING DEPENDING ON COMMENT
 RESPONSES AND NEW INFORMATION SUBMITTED
 AS COMPLETE PLANS ARE SUBMITTED. SECTION
 106.1.1.
 2. TITLE BLOCKS FOR HDR ENGINEERING INC. CERTIFICATE OF
 AUTHORIZATION NUMBER ON
 THE STATE WEBSITE INDICATES THE ADDRESS
 AS 8404 INDIAN HILLS DR. OMAHA NEBRASKA.
 PLEASE INCLUDE THIS ADDRESS ON THE TITLE
 BLOCK OF EACH SHEET AS REQUIRED. (SEE
 ATTACHED SHEET FROM FLORIDA DBPR).
 3. SHT C-09 DDCVA ON 8" DIP WM NOT
 APPROVED FOR THE TYPE OF HIGH HAZARD FOR
 THE INDUSTRIAL SUPPLY WATER MAIN. RPZV
 BACKFLOW REQUIRED. SECTION 608.13.2. -
 ALSO 6" ISWM LINE THAT IS CAPPED OFF
 SHALL HAVE AN RPZV BACKFLOW ON THAT LINE
 AS WELL. PLEASE INDICATE THE LOCATION OF
 THE BACKFLOW FOR THAT LINE. SECTIONS
 608.13.2 AND 106.1.1.
 4. SHT A-01 WATER CLOSETS REQUIRED PER
 TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR
 BUSINESS. SECTION 403.3 STATES THE
 REQUIRED WATER CLOSETS, LAVATORIES, ETC.
 SHALL BE DISTRIBUTED EVENLY BETWEEN THE
 SEXES. FLOOR PLAN INDICATES ONE WATER
 CLOSET IN THE WOMEN'S TOILET ROOM AND
 ONE WATER CLOSET AND TWO URINALS IN THE
 MEN'S TOILET ROOM. PLEASE CLARIFY.
 5. SHT A-05 BREAK ROOM SINK (214) SHALL
 BE ACCESSIBLE. PLEASE SUBMIT A DETAIL
 SHOWING COMPLIANCE WITH SECTION 11-4.24
 AND ALL SUBSECTIONS.
 6. SHT A-05 BREAKROOM ELEVATION
 INDICATOR SHOWS 4/A-19. NO ELEVATION #4
 SHOWN. PLEASE CLARIFY. SECTION 106.1.1.
 7. SHT A-05 DRINKING FOUNTAIN. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 AND ALL SUBSECTIONS AS WELL AS
 SECTION 11-4.1.3(10)(A) PROVISIONS FOR
 THOSE WHO HAVE DIFFICULTY BENDING OR
 STOOPING.
 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE
 AND TURNING AREA IN BOTH TOILET ROOMS
 AND FOR ALL ACCESSIBLE FIXTURES IN BOTH
 TOILET ROOMS.
 9. SHT A-10 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS. SHOW
 SQUARE FOOTAGE BEING DRAINED BY EACH
 PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN
 CALCULATIONS. - SHOW THE LOCATION OF ALL
 OVERFLOW SCUPPERS, AND SIZE OF O/F
 SCUPPERS PER SECTIONS 1101.7, 1107.3 AND
 TABLE 1106.7. THE SIZING OF THE SCUPPERS
 CAN NOT BE DETERMINED WITHOUT REFERENCE
 TO THE DEFLECTION OF THE ROOF. PLEASE
 SHOW O/F SCUPPER CALCULATION ON PLANS
 INDICATING SIZE OF SCUPPERS AND PROVIDE
 DETAIL OF O/F SCUPPERS SHOWING HEIGHT
 AND WIDTH.
 10. SUBMIT MSDS SHEETS FOR ALL HAZARDOUS
 MATERIALS USED AND/OR STORED AT THE
 FACILITY. THIS SHOULD INCLUDE AND
 PRODUCTS PRODUCED AND STORED.
 11. SHT A-18 THE FOLLOWING SHALL BE
 SHOWN ON THE TOILET ROOMS ELEVATIONS:
 FOR W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.5 FLUSH CONTROLS
 FOR LAVS
 A. 11-4.19.3 CLEAR FLOOR SPACE
 B. 11-4.19.5 FAUCETS
 FOR URINALS
 A. 11-4.18.2 HEIGHT
 B. 11-4.18.3 CLEAR FLOOR SPACE
 C. 11-4.18.4 FLUSH CONTROLS
 FOR SHOWERS
 A. 11-4.21.2 SIZE AND CLEARANCES
 B. 11-4.21.3 SEAT (IF INSTALLED)
 C. 11-4.21.4 GRAB BARS
 D. 11-4.21.5 CONTROLS
 E. 11-4.21.6 SHOWER UNIT
 F. 11-4.21.7 CURBS
 12. SHT A-23 ROOM FINISH SCHEDULE, ROOM
 213 INDICATED AS MEN'S RESTROOM, FLOOR
 PLAN SHOW IT AS WOMEN'S RESTROOM. PLEASE CORRELATE.
 SECTION 106.1.1.
 13. PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE MANAGER FOR
 POSSIBLE INTERCEPTORS AND/OR NUTRALIZER
 TANKS. CONTACT HER AT (561) 822-2271,
 (561) 822-2279 (FAX), OR [email protected] (E-MAIL).
 14. P-07 DETAIL NUMBER 3 INDIRECT WASTE,
 AIR GAP BETWEEN THE INDIRECT WASTE PIPE
 AND THE FLOOD LEVEL RIM OF THE WASTE
 RECEPTOR SHALL BE A MINIMUM OF TWICE THE
 EFFECTIVE OPENING OF THE INDIRECT WASTE
 PIPE. SECTION 802.2.1. INDICATE THE PIPE
 SIZE OF ALL INDIRECT WASTE PIPES.
 15. SHT P-07 DETAIL 2 WATER HEATER,
 THERMAL EXPANSION CONTROL REQUIRED PER
 SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC
 "UNIONS" NOT APPROVED FOR
 WATER USAGE. PLEASE CHANGE TO
 "COUPLINGS".
 16. SHT P-08 WATER ISOMETRIC FOR THE
 MAIN LEVEL DOES NOT REFLECT THE PIPING
 SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE
 CORRELATE ISOMETRIC AND FLOW SCHEMATIC.
 SECTION 106.1.1.
 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS, NOR
 DOES IT REFLECT THE FLOOR PLAN SHT P-02.
 TRAPS ARE REQUIRED ON ALL FIXTURES
 EXCEPT THE CLEANOUTS AND THE WATER
 CLOSETS AS THE W/C'S HAVE AN INTEGRAL
 TRAP IN THE FIXTURES. SECTION 1002.1. -
 NO HORIZONTAL DRY VENTS PER SECTIONS
 905.3 & 905.4. - PIPING DOES NOT REFLECT
 THE FLOOR PLAN AT ESEW. NO PIPING SHOWN
 ON THE FLOOR PLAN. SHOW ALL PIPE SIZES
 ON ISOMETRIC. PLEASE CORRELATE RISER AND
 FLOOR PLAN. SECTION 106.1.1.
 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC
 DOES NOT MEET CODE REQUIREMENTS. TRAPS
 ARE REQUIRED ON ALL FIXTURES EXCEPT
 CLEANOUTS AND WATER CLOSETS AS THE W/C'S
 HAVE INTEGRAL TRAPS IN THE FIXTURES. -
 DRY HORIZONTAL VENTS ARE NOT APPROVED
 PER SECTIONS 905.3 & 905.4.- MANY
 FIXTURES ARE NOT VENTED PROPERLY AS
 REQUIRED IN SECTION 901.2.1. (SEE
 EXAMPLE ON THIS SHEET ONE SET OF PLANS)
 - SHOW ALL PIPE SIZES ON THE ISOMETRICS.
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 I. SUBMIT GAS PIPING ON THE FLOOR PLANS
 TO CONFIRM ROUTING OF PLANS SHOWN ON THE ISOMETRIC.
 SECTION 106.1.1.
 20. SUBMIT PLANS FOR THE COMPRESSED AIR
 SYSTEM. SHOW A FLAT DRAWING AND AN
 ISOMETRIC DRAWING WITH ALL PIPE SIZES,
 VALVES, TYPE OF MATERIAL ETC. SECTION 106.3.1.5.3.
 21. SHTS IR-1 THRU IR-5 IF THE DESIGN
 PROFESSIONAL IS AN ARCHITECT OR ENGINEER
 THEN PLANS SHALL BE SIGNED, SEALED, AND
 DATED BY THE DESIGN PROFESSIONAL.
 SECTION 106.1.
 22. ALL DOMESTIC PUMPS AND OR BOOSTER
 PUMPS SHALL BE LISTED. SUBMIT MANUF. SPECIFICATIONS
 SHEETS. SECTION 303.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved