| Date |
Text |
| 2006-03-07 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | PLAN REVIEW ONLY |
| | 1. PLANS INDICATED DOCUMENT 90% COMPLETE |
| | AND AS SUCH MORE COMMENTS MAY BE |
| | FORTHCOMING DEPENDING ON COMMENT |
| | RESPONSES AND NEW INFORMATION SUBMITTED |
| | AS COMPLETE PLANS ARE SUBMITTED. SECTION |
| | 106.1.1. |
| | 2. TITLE BLOCKS FOR HDR ENGINEERING INC. CERTIFICATE OF |
| | AUTHORIZATION NUMBER ON |
| | THE STATE WEBSITE INDICATES THE ADDRESS |
| | AS 8404 INDIAN HILLS DR. OMAHA NEBRASKA. |
| | PLEASE INCLUDE THIS ADDRESS ON THE TITLE |
| | BLOCK OF EACH SHEET AS REQUIRED. (SEE |
| | ATTACHED SHEET FROM FLORIDA DBPR). |
| | 3. SHT C-09 DDCVA ON 8" DIP WM NOT |
| | APPROVED FOR THE TYPE OF HIGH HAZARD FOR |
| | THE INDUSTRIAL SUPPLY WATER MAIN. RPZV |
| | BACKFLOW REQUIRED. SECTION 608.13.2. - |
| | ALSO 6" ISWM LINE THAT IS CAPPED OFF |
| | SHALL HAVE AN RPZV BACKFLOW ON THAT LINE |
| | AS WELL. PLEASE INDICATE THE LOCATION OF |
| | THE BACKFLOW FOR THAT LINE. SECTIONS |
| | 608.13.2 AND 106.1.1. |
| | 4. SHT A-01 WATER CLOSETS REQUIRED PER |
| | TABLE 403.1 ARE 2 FOR FACTORY AND 2 FOR |
| | BUSINESS. SECTION 403.3 STATES THE |
| | REQUIRED WATER CLOSETS, LAVATORIES, ETC. |
| | SHALL BE DISTRIBUTED EVENLY BETWEEN THE |
| | SEXES. FLOOR PLAN INDICATES ONE WATER |
| | CLOSET IN THE WOMEN'S TOILET ROOM AND |
| | ONE WATER CLOSET AND TWO URINALS IN THE |
| | MEN'S TOILET ROOM. PLEASE CLARIFY. |
| | 5. SHT A-05 BREAK ROOM SINK (214) SHALL |
| | BE ACCESSIBLE. PLEASE SUBMIT A DETAIL |
| | SHOWING COMPLIANCE WITH SECTION 11-4.24 |
| | AND ALL SUBSECTIONS. |
| | 6. SHT A-05 BREAKROOM ELEVATION |
| | INDICATOR SHOWS 4/A-19. NO ELEVATION #4 |
| | SHOWN. PLEASE CLARIFY. SECTION 106.1.1. |
| | 7. SHT A-05 DRINKING FOUNTAIN. SUBMIT A |
| | DETAIL SHOWING COMPLIANCE WITH SECTION |
| | 11-4.15 AND ALL SUBSECTIONS AS WELL AS |
| | SECTION 11-4.1.3(10)(A) PROVISIONS FOR |
| | THOSE WHO HAVE DIFFICULTY BENDING OR |
| | STOOPING. |
| | 8. SHT A-08 SHOW THE CLEAR FLOOR SPACE |
| | AND TURNING AREA IN BOTH TOILET ROOMS |
| | AND FOR ALL ACCESSIBLE FIXTURES IN BOTH |
| | TOILET ROOMS. |
| | 9. SHT A-10 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. SHOW |
| | SQUARE FOOTAGE BEING DRAINED BY EACH |
| | PRIMARY ROOF DRAIN. SHOW 1/2 AREA OF ALL |
| | VERTICAL WALLS INCLUDING PARAPETS IN |
| | CALCULATIONS. - SHOW THE LOCATION OF ALL |
| | OVERFLOW SCUPPERS, AND SIZE OF O/F |
| | SCUPPERS PER SECTIONS 1101.7, 1107.3 AND |
| | TABLE 1106.7. THE SIZING OF THE SCUPPERS |
| | CAN NOT BE DETERMINED WITHOUT REFERENCE |
| | TO THE DEFLECTION OF THE ROOF. PLEASE |
| | SHOW O/F SCUPPER CALCULATION ON PLANS |
| | INDICATING SIZE OF SCUPPERS AND PROVIDE |
| | DETAIL OF O/F SCUPPERS SHOWING HEIGHT |
| | AND WIDTH. |
| | 10. SUBMIT MSDS SHEETS FOR ALL HAZARDOUS |
| | MATERIALS USED AND/OR STORED AT THE |
| | FACILITY. THIS SHOULD INCLUDE AND |
| | PRODUCTS PRODUCED AND STORED. |
| | 11. SHT A-18 THE FOLLOWING SHALL BE |
| | SHOWN ON THE TOILET ROOMS ELEVATIONS: |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS |
| | A. 11-4.19.3 CLEAR FLOOR SPACE |
| | B. 11-4.19.5 FAUCETS |
| | FOR URINALS |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | FOR SHOWERS |
| | A. 11-4.21.2 SIZE AND CLEARANCES |
| | B. 11-4.21.3 SEAT (IF INSTALLED) |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | E. 11-4.21.6 SHOWER UNIT |
| | F. 11-4.21.7 CURBS |
| | 12. SHT A-23 ROOM FINISH SCHEDULE, ROOM |
| | 213 INDICATED AS MEN'S RESTROOM, FLOOR |
| | PLAN SHOW IT AS WOMEN'S RESTROOM. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | 13. PLEASE CONTACT LYNN MASSON, |
| | ENVIRONMENTAL COMPLIANCE MANAGER FOR |
| | POSSIBLE INTERCEPTORS AND/OR NUTRALIZER |
| | TANKS. CONTACT HER AT (561) 822-2271, |
| | (561) 822-2279 (FAX), OR [email protected] (E-MAIL). |
| | 14. P-07 DETAIL NUMBER 3 INDIRECT WASTE, |
| | AIR GAP BETWEEN THE INDIRECT WASTE PIPE |
| | AND THE FLOOD LEVEL RIM OF THE WASTE |
| | RECEPTOR SHALL BE A MINIMUM OF TWICE THE |
| | EFFECTIVE OPENING OF THE INDIRECT WASTE |
| | PIPE. SECTION 802.2.1. INDICATE THE PIPE |
| | SIZE OF ALL INDIRECT WASTE PIPES. |
| | 15. SHT P-07 DETAIL 2 WATER HEATER, |
| | THERMAL EXPANSION CONTROL REQUIRED PER |
| | SECTION 607.3.2. PLEASE INDICATE MENTOD. DIELECTRIC |
| | "UNIONS" NOT APPROVED FOR |
| | WATER USAGE. PLEASE CHANGE TO |
| | "COUPLINGS". |
| | 16. SHT P-08 WATER ISOMETRIC FOR THE |
| | MAIN LEVEL DOES NOT REFLECT THE PIPING |
| | SHOWN ON SHT P-01 FLOW SCHEMATIC. PLEASE |
| | CORRELATE ISOMETRIC AND FLOW SCHEMATIC. |
| | SECTION 106.1.1. |
| | 17. SHT P-10 DRAINAGE PLUMBING ISOMETRIC |
| | DOES NOT MEET CODE REQUIREMENTS, NOR |
| | DOES IT REFLECT THE FLOOR PLAN SHT P-02. |
| | TRAPS ARE REQUIRED ON ALL FIXTURES |
| | EXCEPT THE CLEANOUTS AND THE WATER |
| | CLOSETS AS THE W/C'S HAVE AN INTEGRAL |
| | TRAP IN THE FIXTURES. SECTION 1002.1. - |
| | NO HORIZONTAL DRY VENTS PER SECTIONS |
| | 905.3 & 905.4. - PIPING DOES NOT REFLECT |
| | THE FLOOR PLAN AT ESEW. NO PIPING SHOWN |
| | ON THE FLOOR PLAN. SHOW ALL PIPE SIZES |
| | ON ISOMETRIC. PLEASE CORRELATE RISER AND |
| | FLOOR PLAN. SECTION 106.1.1. |
| | 18. SHT P-11 DRAINAGE PLUMBING ISOMETRIC |
| | DOES NOT MEET CODE REQUIREMENTS. TRAPS |
| | ARE REQUIRED ON ALL FIXTURES EXCEPT |
| | CLEANOUTS AND WATER CLOSETS AS THE W/C'S |
| | HAVE INTEGRAL TRAPS IN THE FIXTURES. - |
| | DRY HORIZONTAL VENTS ARE NOT APPROVED |
| | PER SECTIONS 905.3 & 905.4.- MANY |
| | FIXTURES ARE NOT VENTED PROPERLY AS |
| | REQUIRED IN SECTION 901.2.1. (SEE |
| | EXAMPLE ON THIS SHEET ONE SET OF PLANS) |
| | - SHOW ALL PIPE SIZES ON THE ISOMETRICS. |
| | 19. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - INDICATE ON PLANS TABLE |
| | BEING USED OF ALL GAS PIPING. |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | F. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | I. SUBMIT GAS PIPING ON THE FLOOR PLANS |
| | TO CONFIRM ROUTING OF PLANS SHOWN ON THE ISOMETRIC. |
| | SECTION 106.1.1. |
| | 20. SUBMIT PLANS FOR THE COMPRESSED AIR |
| | SYSTEM. SHOW A FLAT DRAWING AND AN |
| | ISOMETRIC DRAWING WITH ALL PIPE SIZES, |
| | VALVES, TYPE OF MATERIAL ETC. SECTION 106.3.1.5.3. |
| | 21. SHTS IR-1 THRU IR-5 IF THE DESIGN |
| | PROFESSIONAL IS AN ARCHITECT OR ENGINEER |
| | THEN PLANS SHALL BE SIGNED, SEALED, AND |
| | DATED BY THE DESIGN PROFESSIONAL. |
| | SECTION 106.1. |
| | 22. ALL DOMESTIC PUMPS AND OR BOOSTER |
| | PUMPS SHALL BE LISTED. SUBMIT MANUF. SPECIFICATIONS |
| | SHEETS. SECTION 303.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 653-2692 |
| | E-MAIL [email protected] |