| 2006-02-16 00:00:00 | DENIED: **** PLAN REVIEW ONLY *** |
| | |
| | INDEX PLAN SHEET & COVER SHEET FOR THE |
| | SPEC BOOK INDICATES 90% REVIEW.PLEASE |
| | NOTE, INCOMPLETE SUBMITTAL MAY GENERATE |
| | ADDITIONAL COMMENTS UPON COMPLETION OF |
| | PLANS & SPECIFICATIONS AS WELL AS |
| | RESPONSES TO REVIEW COMMENTS. |
| | |
| | 1.PLEASE CLARIFY THE RATING OF THE |
| | WALL BETWEEN THE MAIN PROCESSING (107) & |
| | SLUDGE STORAGE (103).48" X 48" DUCT |
| | PENETRATING THIS WALL IS THIS TRANSFER |
| | DUCT? |
| | |
| | 2.PLAN SHEET M-03 MAKE-UP AIR FROM |
| | STAIR INTO ROOM (NOT IDENTIFIED ON THE |
| | PARTIAL LOWER LEVEL HVAC PLAN). PLEASE |
| | ALSO INDICATE WHERE EF-04 TERMINATES & |
| | AT WHAT ELEVATION.PLEASE IDENTIFY THIS |
| | ROOM.IS THIS A RATED WALL? |
| | |
| | 3.PLAN SHEET M-03 PROVIDE ELEVATION & |
| | TERMINATION POINT OF EF-05. |
| | |
| | 4.PLEASE PROVIDE COMBUSTION AIR |
| | CALCULATIONS PER 2004 FMC CHAPTER 7. |
| | PLEASE PROVIDE ADDITIONAL INFORMATION ON |
| | THE 2 "FURNANCES" INDICATED ON PLAN |
| | SHEET E-11.THESE ARE NOT INDICATED ON |
| | AN EQUIPMENT SCHEDULE. |
| | |
| | 5.PLEASE PROVIDE MSDS SHEETS FOR ALL |
| | CHEMICALS THAT WILL BE UTILIZED OR |
| | STORED AT THE SITE.PLEASE PROVIDE |
| | INFORMATION ON STORAGE OF CHEMICALS. |
| | |
| | 6.PLAN SHEET D-04 INDICATES AN |
| | EMERGENCY GENERATOR.NOTE 1 REFERS TO |
| | CIVIL DRAWINGS FOR LOCATION.CIVIL |
| | DRAWINGS TO NOT INDICATE LOCATION. |
| | PLEASE PROVIDE DISTANCES FROM BUILDING, |
| | PROPERTY LINES AND FRESH AIR INTAKES. |
| | |
| | 7.PLEASE PROVIDE A OUTSIDE AIR |
| | CALCULATIONS & AIR BALANCE SCHEDULE. |
| | |
| | 8.PLUMBING PLANS INDICATE GAS WATER |
| | HEATER.PLEASE PROVIDE GAS PLANS. |
| | |
| | 9.FAN SHUTDOWN BY DUCT SMOKE DETECTOR |
| | WITH NOTIFICATION TO ALARM/STROBE IN |
| | NORMALLY OCCUPIED AREAS.2004 FMC |
| | 606.2.1. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |