| Date |
Text |
| 2006-07-01 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 19. THE FOLLOWING INFORMATION IS |
| | REQUIRED FOR THE GAS PERMIT: |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS. |
| | ***RESPONSE NOTED, BUT SOME SECTION DO |
| | NOT INDICATE THE LENGHTS. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | ***RESPONSE NOTED, BUT INDICATE IF ALL |
| | PIPE IS WELDED. (NATURAL GAS PIPE NOT |
| | INDICATED). WELDING CERTIFICATE AND |
| | WELDING PROCEDURE REQUIRED AT TIME OF |
| | APPLICATION. |
| | |
| | C. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). - INDICATE ON PLANS TABLE |
| | BEING USED OF ALL GAS PIPING. |
| | ***RESPONSE NOTED, BUT THE TABLE USED |
| | FOR SIZING THE PIPE SHALL BE SUBMITTED |
| | WITH PLANS. |
| | |
| | D. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | ***RESPONSE NOTED, BUT TOTAL DEVELOPED |
| | LENGTH IS NOT SHOWN, AND CAN NOT BE |
| | VERIFIED UNTIL ALL CUT SECTION |
| | MEASUREMENTS ARE SHOWN. |
| | |
| | E. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | ***NO RESPONSE TO THIS COMMENT FOUND. |
| | |
| | G. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | ***NO RESPONSE NOTED. |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ***NO RESPONSE NOTED. |
| | |
| | **************NEW COMMENTS************** |
| | |
| | 2B. FOR THE GAS SYSTEM: SUBMIT MANUF. |
| | SPECIFICATIONS FOR THE REGULATORS USED. |
| | INDICATE IF THE REGULATOR WILL BE VENTED |
| | AND IF SO INDICATE THE MATERIAL USED FOR |
| | THE VENT. ALSO SHOW VENTING ROUTE FOR |
| | REGULATOR. SECTION 106.1.1. |
| | |
| | 3B. FOR THE GAS SYSTEM: SLEEVES ARE |
| | REQUIRED WHERE THE GAS ENTERS THE |
| | BUILDING. SECTION 404.7. |
| | |
| | 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW |
| | THE PIPING TO FU101 & FU201. SHOW SHUT |
| | OFF VALVES AND DRIP LINES FOR ALL UNITS. |
| | SECTIONS 408.2, 408.4, 409.4 & 409.5. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |