Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop G
Sequence Number 1
Notes
Date Text
2006-07-01 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 FROM PREVIOUS REVIEW:
  
 19. THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 ***RESPONSE NOTED, BUT SOME SECTION DO
 NOT INDICATE THE LENGHTS.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ***RESPONSE NOTED, BUT INDICATE IF ALL
 PIPE IS WELDED. (NATURAL GAS PIPE NOT
 INDICATED). WELDING CERTIFICATE AND
 WELDING PROCEDURE REQUIRED AT TIME OF
 APPLICATION.
  
 C. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). - INDICATE ON PLANS TABLE
 BEING USED OF ALL GAS PIPING.
 ***RESPONSE NOTED, BUT THE TABLE USED
 FOR SIZING THE PIPE SHALL BE SUBMITTED
 WITH PLANS.
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 ***RESPONSE NOTED, BUT TOTAL DEVELOPED
 LENGTH IS NOT SHOWN, AND CAN NOT BE
 VERIFIED UNTIL ALL CUT SECTION
 MEASUREMENTS ARE SHOWN.
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
 ***NO RESPONSE TO THIS COMMENT FOUND.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
 ***NO RESPONSE NOTED.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ***NO RESPONSE NOTED.
  
 **************NEW COMMENTS**************
  
 2B. FOR THE GAS SYSTEM: SUBMIT MANUF.
 SPECIFICATIONS FOR THE REGULATORS USED.
 INDICATE IF THE REGULATOR WILL BE VENTED
 AND IF SO INDICATE THE MATERIAL USED FOR
 THE VENT. ALSO SHOW VENTING ROUTE FOR
 REGULATOR. SECTION 106.1.1.
  
 3B. FOR THE GAS SYSTEM: SLEEVES ARE
 REQUIRED WHERE THE GAS ENTERS THE
 BUILDING. SECTION 404.7.
  
 4B. FOR THE GAS SYSTEM: SHT P-12 SHOW
 THE PIPING TO FU101 & FU201. SHOW SHUT
 OFF VALVES AND DRIP LINES FOR ALL UNITS.
 SECTIONS 408.2, 408.4, 409.4 & 409.5.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  