| 2006-03-14 00:00:00 | DENIED: |
| | |
| | 1) THE NFPA STANDARD ON SHEET #G-04 |
| | GENERAL NOTES #1 IS INCORRECT. THE |
| | CORRECT STANDARD IS NFPA 820 STANDARD |
| | FOR FIRE PROTECTION IN WASTEWATER |
| | TREATMENT AND COLLECTION FACILITIES.( |
| | ALSO INDICATE ON SHEET #A-01 UNDER CODE |
| | SUMMARY. |
| | |
| | 2) SHALL COMPLY WITH NFPA 101 LIFE |
| | SAFETY CODE, 2003 EDITION AND NFPA 1 |
| | UNIFORM FIRE CODE, 2003 EDITION. ( |
| | PLEASE INDICATE ON SHEET # A-01 UNDER |
| | CODE SUMMARY ) |
| | |
| | 3) THE EMERGENCY GENERATOR SHALL COMPLY |
| | WITH NFPA 110 STANDARD FOR EMERGENCY AND |
| | STANDBY POWER SYSTEMS, 2002 EDITION. |
| | |
| | 4) FIRE PROTECTION MEASURES DURING |
| | CONSTRUCTION AT BOTH NEW AND EXISTING |
| | WASTEWATER FACILITIES SHALL BE PROVIDED |
| | IN ACCORDANCE WITH NFPA 241. |
| | |
| | 5) THIS FACILITIE IS REQUIRED TO HAVE A |
| | FIRE RISK EVALUATION, FIRE PREVENTION |
| | PROGRAM, AND FIRE EMERGENCY PLAN. |
| | |
| | 6) SEPARATE PLANS AND PERMIT |
| | APPLICATIONS ARE REQUIRED FOR FIRE |
| | SPRINKLER AND FIRE ALARM SYSTEMS |
| | INSTALLATION. |
| | |
| | 7) WHERE UNDERGROUND WATER MAINS AND |
| | HYDRANTS ARE TO BE PROVIDED, THEY SHALL |
| | BE INSTALLED, COMPLETED, AND IN SERVICE |
| | PRIOR TO CONSTRUCTION WORK. |
| | |
| | |
| | NATE MCCRAY, ASSISTANT FIRE MARSHAL |