Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-14 00:00:00DENIED:
  
 1) THE NFPA STANDARD ON SHEET #G-04
 GENERAL NOTES #1 IS INCORRECT. THE
 CORRECT STANDARD IS NFPA 820 STANDARD
 FOR FIRE PROTECTION IN WASTEWATER
 TREATMENT AND COLLECTION FACILITIES.(
 ALSO INDICATE ON SHEET #A-01 UNDER CODE
 SUMMARY.
  
 2) SHALL COMPLY WITH NFPA 101 LIFE
 SAFETY CODE, 2003 EDITION AND NFPA 1
 UNIFORM FIRE CODE, 2003 EDITION. (
 PLEASE INDICATE ON SHEET # A-01 UNDER
 CODE SUMMARY )
  
 3) THE EMERGENCY GENERATOR SHALL COMPLY
 WITH NFPA 110 STANDARD FOR EMERGENCY AND
 STANDBY POWER SYSTEMS, 2002 EDITION.
  
 4) FIRE PROTECTION MEASURES DURING
 CONSTRUCTION AT BOTH NEW AND EXISTING
 WASTEWATER FACILITIES SHALL BE PROVIDED
 IN ACCORDANCE WITH NFPA 241.
  
 5) THIS FACILITIE IS REQUIRED TO HAVE A
 FIRE RISK EVALUATION, FIRE PREVENTION
 PROGRAM, AND FIRE EMERGENCY PLAN.
  
 6) SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS
 INSTALLATION.
  
 7) WHERE UNDERGROUND WATER MAINS AND
 HYDRANTS ARE TO BE PROVIDED, THEY SHALL
 BE INSTALLED, COMPLETED, AND IN SERVICE
 PRIOR TO CONSTRUCTION WORK.
  
  
 NATE MCCRAY, ASSISTANT FIRE MARSHAL