Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-03 00:00:001.PLEASE DOCUMENT THE CLASS LOCATIONS
 PER 500.4(A).
  
 2.HAVING READ YOUR BOOK ON THE LOCATION
 IT DOES NOT PROVIDE ENOUGH INFORMATION
 TO THE CITY TO NOT CLASSIFY THESE
 LOCATIONS.
  
 3.IF YOU READ 500.8 IT CALLS FOR THE
 PROPER MAINTENANCE OF THE EQUIPMENT,
 THAT WAS ONE OF THE POINTS IN YOUR
 PRESENTATION THAT YOU WOULD PROVIDE GOOD
 HOUSEKEEPING, NOT ONLY DO YOU HAVE
 TO,IT'S A REQUIREMENT.
  
 4.SHUNT TRIPS ARE SHOWN, WHERE ARE THEY
 GOING TO BE LOCATED AND WHY/
  
 5.SERVICE SHOWS TWO 4000A AMPERE MAINS
 NO GFI PROTECTION PLEASE INDICATE WHY
 NONE IS PROVIDED. SEE 230.95
  
 6.GENERATOR DISCONNECT SHALL BE READILY
 ACCESSIBLE AND WITHIN 50' OF THE
 BUILDING OR ANOTHER MEANS OF DISCONNECT
 WILL BE REQUIRED.225.32
  
 7.LOAD CALCULATION IS VAGUE PLESE SHOW
 HOW LOAD CALCULATION WAS DONE IN
 ACCORDANCE WITH ARTICLE 220, NEED
 CALCULATION FOR SWB1,2 MCC 1-4,
 GENERATOR.
  
 8.MCCS SHOW HOW BRANCH CIRCUIT
 PROTECTION WAS DONE AND THE MULTIPLIER
 USED FOR THE PROTECTION. 430.52, 430.6A1
  
 9.WHAT TYPE OF PROTECTION IS BEING USED
 FOR THE BRANCH CIRCUITS IN THE MCCS.
  
 10.SEE 500.5B2 FOR TYPES OF LOCATIONS
 CONSIDERED HAZARDOUS SEE 1,2,3. THIS
 LOOKS TO BE THE TYPE OF SYSTEM BEING
 INSTALLED. THROUGH GOOD HOUSEKEEPING AND
 YOUR DESIGN YOU CAN NOT SHOW THAT AN
 ACCIDENT OR FAILURE OF THE SYSTEM WILL
 NEVERIT WILL BE THE RECOMENDATION OF
 THIS PLAN REVIEWER THAT THE AREA BE
 CLASSIFIED CLASS 1 DIVISION 2.
  
 QUESTIONS CALL JAKE LEAHY
 561-644-7291
  