| 2006-03-03 00:00:00 | 1.PLEASE DOCUMENT THE CLASS LOCATIONS |
| | PER 500.4(A). |
| | |
| | 2.HAVING READ YOUR BOOK ON THE LOCATION |
| | IT DOES NOT PROVIDE ENOUGH INFORMATION |
| | TO THE CITY TO NOT CLASSIFY THESE |
| | LOCATIONS. |
| | |
| | 3.IF YOU READ 500.8 IT CALLS FOR THE |
| | PROPER MAINTENANCE OF THE EQUIPMENT, |
| | THAT WAS ONE OF THE POINTS IN YOUR |
| | PRESENTATION THAT YOU WOULD PROVIDE GOOD |
| | HOUSEKEEPING, NOT ONLY DO YOU HAVE |
| | TO,IT'S A REQUIREMENT. |
| | |
| | 4.SHUNT TRIPS ARE SHOWN, WHERE ARE THEY |
| | GOING TO BE LOCATED AND WHY/ |
| | |
| | 5.SERVICE SHOWS TWO 4000A AMPERE MAINS |
| | NO GFI PROTECTION PLEASE INDICATE WHY |
| | NONE IS PROVIDED. SEE 230.95 |
| | |
| | 6.GENERATOR DISCONNECT SHALL BE READILY |
| | ACCESSIBLE AND WITHIN 50' OF THE |
| | BUILDING OR ANOTHER MEANS OF DISCONNECT |
| | WILL BE REQUIRED.225.32 |
| | |
| | 7.LOAD CALCULATION IS VAGUE PLESE SHOW |
| | HOW LOAD CALCULATION WAS DONE IN |
| | ACCORDANCE WITH ARTICLE 220, NEED |
| | CALCULATION FOR SWB1,2 MCC 1-4, |
| | GENERATOR. |
| | |
| | 8.MCCS SHOW HOW BRANCH CIRCUIT |
| | PROTECTION WAS DONE AND THE MULTIPLIER |
| | USED FOR THE PROTECTION. 430.52, 430.6A1 |
| | |
| | 9.WHAT TYPE OF PROTECTION IS BEING USED |
| | FOR THE BRANCH CIRCUITS IN THE MCCS. |
| | |
| | 10.SEE 500.5B2 FOR TYPES OF LOCATIONS |
| | CONSIDERED HAZARDOUS SEE 1,2,3. THIS |
| | LOOKS TO BE THE TYPE OF SYSTEM BEING |
| | INSTALLED. THROUGH GOOD HOUSEKEEPING AND |
| | YOUR DESIGN YOU CAN NOT SHOW THAT AN |
| | ACCIDENT OR FAILURE OF THE SYSTEM WILL |
| | NEVERIT WILL BE THE RECOMENDATION OF |
| | THIS PLAN REVIEWER THAT THE AREA BE |
| | CLASSIFIED CLASS 1 DIVISION 2. |
| | |