Plan Review Notes
Plan Review Notes For Permit 05120429
Permit Number 05120429
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-28 00:00:00****CORRECTIONS****
 ****PLAN REVIEW ONLY****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION (PERMIT ONLY).
  
 2.)PROVIDE A SOILS INVESTIGATION
 REPORT FBC1802.2.
  
 3.)THREE COPIES OF ALL PERMIT
 DOCUMENTS REQUIRED, SEE ITEM 4 BELOW.
  
 4.) FBC* 109.3.7RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 ALSO, PLEASE ARRANGE WITH HAROLD PISKURA
 (INSPECTION SERVICES MANAGER - TEL:
 561 805 6711), A MEETING INVOLVING THE
 OWNER, RESIDENT INSPECTOR, JOB
 INSPECTOR, CONTRACTOR AND ENGINEER.
  
 5.)PROVIDE A FLOOD ZONE DESIGNATION
 FOR THIS PARCEL.CITY OF WEST PALM
 BEACH MUNICIPAL CODE 94-546(B) REQUIRES
 FFE TO BE 6IN ABOVE BASE FLOOD ELEVATION
 FOR IMPROVEMENTS IN THE HIGH HAZARD
 FLOOD ZONE AREAS.NOTE MINIMUM
 ELEVATION ON THE PLAN IF APPLICABLE.
  
 6.)PARKING SPACE STRIPING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARDS,
 C12, SEE ATTACHED DETAIL.
  
 7.) A01 DECLARES F3 OCCUPANCY.SEE NFPA
 820 REGARDING THE FIRE HAZARD ASSOCIATED
 WITH THIS TYPE OF FACILITY.THE CORRECT
 OCCUPANCY WOULD BE H.NOT ENOUGH
 INFORMATION HAS BEEN PROVIDED ABOUT THE
 MATERIALS PROCESSED AND THE END PRODUCT
 TO DETERMINE THE CORRECT SUB
 CLASSIFICATION.PROVIDE INFORMATION
 ABOUT THE MATERIALS STORED IN THE
 BUILDING, MATERIALS USED IN PROCESSING,
 FLAMMABLE GASES PRODUCED, AND THE END
 PRODUCT AS RELATED TO OCCUPANCY
 CLASSIFICATION.DECLARE OCCUPANCY
 CLASSIFICATION, FBC307, SEE ALSO
 FBC307.8 REGARDING MULTIPLE HAZARDS, AND
 NFPA 820 1.3.5, MATERIALS USED FOR ANTI
 CORROSION WHICH MAY CAUSE ACCELERATED
 BURNING.
  
 IN ORDER TO ASSIST IN DETERMINING
 CORRECT OCCUPANCY CLASSIFICATION, PLEASE
 ADDRESS THIS ITEM IN A SIGNED, SEALED
 AND DATED LETTER FROM ONE OF THE DESIGN
 PROFESSIONALS WITH THE ASSOCIATED
 DOCUMENTATION, INCLUDING MSDS IF
 AVAILABLE.
  
 8.)REVISE OTHER ITEMS A01, CODE
 SUMMARY WHICH ARE AFFECTED BY THE
 OCCUPANCY CLASSIFICATION AND REVISE
 PLANS ACCORDINGLY (BUILDING HEIGHT AND
 AREA, OCCUPANT LOAD, ETC.).NOTE THAT
 DUE TO A LACK OF A CORRECT OCCUPANCY
 CLASSIFICATION A COMPLETE CHECKLIST
 CANNOT BE PROVIDED AT THIS TIME.
  
 9.)REVISE OCCUPANT LOAD FBC1004.A01
 PROVIDES AN OCCUPANT LOAD BUT IS NOT
 CLEAR AS TO THE OCCUPANCY OF THE
 DIFFERENT AREAS.PROVIDE SQUARE FOOT
 BUSINESS AREA, AND OCCUPANT LOAD.
  
 10.)CODE COMPLIANCE WITH FBC TABLE
 503, CANNOT BE DETERMINED WITHOUT THE
 CORRECT OCCUPANCY CLASSIFICATION.IF
 YOU ARE USING AN AREA INCREASE, PROVIDE
 CALCULATIONS FBC506.
  
 11.)PROVIDE MSDS FOR EACH MATERIAL
 USED FOR PROCESSING AND FOR THE END
 PRODUCT.
  
 12.)E12 SHOWS SULFURIC ACID STORAGE AT
 THE STAIR AND CHEMICAL STORAGE IN THE
 CONTROL ROOM.THIS APPEARS TO BE IN
 CONFLICT WITH OTHER DETAILS WHICH SHOW
 THIS OUTSIDE.CLARIFY.
  
 13.)PROVIDE AN ARCHITECTURAL SITE
 PLAN.SHOW DIMENSIONS TO THE LOT LINES
 OR OTHER STRUCTURES, FBC TABLE 602.
 SHOW THE ACCESSIBLE ROUTE
 FBC11-4.1.2(1).
  
 14.)PROVIDE FIRE SPRINKLER PLANS,
 FBC*106.3.5.1.1(5)
  
 15.)S01 DECLARES THIS BUILDING AS A
 TYPE II ESSENTIAL FACILITY, IMPORTANCE
 FACTOR 1.0.SEE FBC TABLE 1604.5.
 ESSENTIAL FACILITIES ARE TO BE A TYPE
 IV, 1.15 WIND FACTOR.REVISE TO MAKE
 THE LANGUAGE CONSISTENT WITH THE TYPE
 AND FACTOR DECLARED.IF THIS IS NOT
 DECLARED TYPE IV, PLEASE PROVIDE
 RATIONALE.
  
 16.)PROVIDE A LIFE SAFETY PLAN, FBC10.
  
 17.)IT APPEARS THAT THE SLUDGE STORAGE
 AREAS TRAVEL DISTANCES EXCEED THE COMMON
 PATH OF TRAVEL FBC1013.3, TRAVEL
 DISTANCE FBC TABLE 1015.ON THE LIFE
 SAFETY PLAN, CLEARLY SHOW EXITING FOR
 EACH AREA.
  
 18.)PROVIDE MINIMUM DIMENSION FOR ALL
 EGRESS COMPONENTS ON THE FLOOR PLAN.
 FOR INSTANCE, ON THE MEZZANINE LEVEL,
 THE WALKWAY LEADING TO STAIR 5, ALL
 EGRESS STAIRS.
  
 19.)PROVIDE FIRE RATING IN TIME RATHER
 THAN (OR IN ADDITION TO) LETTER RATING,
 FBC TABLE 715.3, A22.
  
 20.)IT IS NOT CLEAR WHAT THE USE OF
 THE AREA WITH EQUIPMENT BS302, BS302,
 F301, F302 IS FOR.PLEASE CLARIFY.IT
 DOES NOT APPEAR ON THE MATERIAL FLOW
 SHEETS OR ON OTHER SECTIONS.
  
 21.)IT IS NOT CLEAR UNDER WHICH
 EXCEPTION TO THE OPENNESS REQUIREMENT
 FOR MEZZANINES APPLIES TO THIS PROJECT,
 FBC505.4, IF ANY.IF THIS IS NOT A
 MEZZANINE IT MUST BE DECLARED AS A TWO
 STORY BUILDING.PLEASE SHOW CODE
 COMPLIANCE ON THE PLAN.
  
 22.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISH CLASSIFICATION, FBC
 TABLE 803.5.
  
 23.)PROVIDE PRODUCT APPROVALS FOR
 COMPONENTS AND CLADDING.ALL PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD FBC*106.3.3.
  
 PLEASE NOTE THAT FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED IN ADDITION TO
 THE EVALUATION REPORT, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 IF FLORIDA STATE PRODUCT APPROVAL IS NOT
 AVAILABLE FOR ANY OF THE COMPONENTS AND
 CLADDING CHOSEN FOR THIS PROJECT, PLEASE
 CONTACT ME FOR ASSISTANCE.
  
 24.)ACCESSIBLE ROUTE REQUIRED
 CONNECTING ALL ACCESSIBLE SPACES,
 FBC11-4.1.3(1).NOTE THAT THERE IS NO
 ACCESSIBLE ROUTE FROM THE SLUDGE
 RECEIVING AREA 109 TO THE SLUDGE
 RECEIVING 108, TO THE MAIN PROCESSING
 AREA 107, ELEVATOR AT LANDING 101.SEE
 ALSO FBC11-4.1.1(1)(3) REGARDING WORK
 AREAS.
  
 25.)THE SLUDGE STORAGE AREA SHOWS
 EQUIPMENT.IS THIS A STORAGE AREA OR A
 WORK AREA?
  
 26.)THE STAIR SECTIONS A07HANDRAIL
 DETAILS DO NOT COMPLY WITH
 FBC11-4.9.4(2) AND (6), BOTTOM.SEE
 ALSO FBC FIGURE 11-19.
  
 27.)NO STAIR TREAD AND RISER
 DIMENSIONS SHOWN (REQUIRES
 CALCULATIONS).PROVIDE DIMENSIONS SO
 THAT DESIGN CRITERIA AND CODE COMPLIANCE
 ARE CLEARLY SHOWN, FBC1009.3.
  
 28.)IT APPEARS THAT THE SECTION FOR
 THE BREAK ROOM HAS AN INCORRECT
 REFERENCE ON A05 (4-A19 RATHER THAN
 DA19).
  
 29.)D-A19, BREAK ROOM SINK IS TO
 COMPLY WITH FBC11-4.24.SHOW ALL
 DETAILS.NOTE THAT CABINET DOORS NOT
 ALLOWED AS IT PREVENTS COMPLIANCE WITH
 FBC11-4.24.3, KNEE CLEARANCE.
  
 30.)PROVIDE DETAILS FOR THE UL
 ASSEMBLIES SPECIFIED.
  
 31.)PROVIDE DESIGN LOAD CRITERIA FOR
 THE VARIOUS AREAS OF THE MEZZANINE AREA,
 FBC16, ROOF.
  
 32.)SEPARATE PERMITS REQUIRED FOR THE
 OTHER STRUCTURES SHOWN ON THE PLAN (FOR
 INSTANCE, THE STORAGE SILOS AND THE
 STEEL STRUCTURE).NO PLANS OR OTHER
 INFORMATION PROVIDED.
  
 33.)E01 STATES THAT CALCULATIONS FOR
 THE LIGHT POLE WILL BE REQUIRED.NOTE
 THAT CALCULATIONS FOR THE LIGHT FIXTURE
 ARE REQUIRED ALSO.
  
 34.)THE SIGNATURES ON THE ELECTRICAL
 SHEETS APPEAR TO BE A PHOTOCOPY OF A
 STAMP.WET SIGNATURE REQUIRED PER FBPE.
  
 35.)THE IR SHEETS ARE NOT SIGNED,
 SEALED AND DATED.
  
 36.)THIS PLAN IS NOTED AS 90% REVIEW.
 NOTE THAT ADDITIONAL INFORMATION MAY
 ALSO TRIGGER NEW COMMENTS.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved