2005-12-19 00:00:00*** DENIED ***
 1) RETURN AIR IS REQUIRED IN NEW OFFICE
 #2, PER 2004 FBC/M 601.4 .
  
 2) NO DUCT OR DUCT SIZE SHOWING FOR
 RETURN AIR GRILL IN NEW OFFICE #1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.