| Plan Review Notes For Permit 05120367 |
| Permit Number |
05120367 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-19 00:00:00 | ******DENIED****** | | | | | | 1) STAIRS AND RAMPS SHALL HAVE HANDRAILS | | | ON BOTH SIDES. | | | | | | 2) ADDRESS IS REQUIRED ON BUILDING AND | | | SHALL BE AT LEAST 6" IN HEIGHT AND | | | CONTRASTING TO THE BACKGROUND. | | | | | | 3) 2A-10BC RATED FIRE EXTINGUISHERS ARE | | | REQUIRED AND SHALL BE SPACED TO MEET THE | | | 75FT. DISTANCE REQUIREMENT. | | | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, | | | 2003 EDITION. | | | | | | 5) SITE PLAN REFLECTS (2) BUILDINGS, | | | HOWEVER IT APPEARS THAT THE SCOPE OF | | | WORK ONLY APPLIES TO THE LARGER BUILDING | | | PLEASE VERIFY. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|