| 2006-01-10 00:00:00 | *** UNSAT *** | | | | | | 1)NOTE: PLEASE SEE PLANS SHOULD REFLECT | | | THE CURRENT NFPA-70,72,101 ETC IN | | | EFFECT. | | | 2002,2002,2003 | | | | | | 2)NOTE: PLEASE SEE BLDG REVIEW COMMENTS | | | AS THE PRINTED LICENSE # IS ALSO | | | REQUIRED FOR ALL SHEETS DONE BY TF | | | KENNEDY. | | | FAC 61G15-23.002 | | | | | | 3)NOTE: PLEASE EITHER MOVE WATER HEATER | | | OR PROVIDE PERMANANT CONSTRUCTION | | | BARRIER FROM COMBUSTIBLES/EASILY | | | IGNITIBLE MATERIALS.422.17 . | | | | | | 4)NOTE: PLEASE VERIFY NEW OR EXISTING | | | REQUIRED SIGN CIRCUIT. | | | 600.5 | | | | | | 5)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE INCLUDE ALL CONTINUOUS LOADS AT | | | 125%. | | | 220.10,220.11,220.13,215.3,230.42 ETC. | | | | | | 6)NOTE: PLEASE SEE RISER SEEMS TO | | | INDICATE THE FOOTER/BLDG STEEL TO BE | | | PART OF THE GROUNDING ELECTRODE SYSTEM. | | | PLEASE VERIFY AS THIS SEEMS TO BE AN | | | EXISTING BLDG AND THE FOOTER STEEL WOULD | | | NOT BE REQUIRED. IT IS PERMITTED , | | | HOWEVER NOT REQUIRED FOR EXISTING BLDGS. | | | TWO GRND RODS WOULD BE REQUIRED. | | | 250.50 | | | | | | | | | PLEASE SEE ANY OTHER COMMENTS FROM OTHER | | | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL | | | PLANS. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|