Plan Review Notes
Plan Review Notes For Permit 05120306
Permit Number 05120306
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-30 00:00:00DENIED
  
 REFERENCE: FBC-2004 424.2 SWIMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) FBC-2004 SEC 424.2.6.6 ENTRAPMENT
 PROTECTION FOR SUCTION INLETS. (DETAIL)
 2) FBC-2004424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 3) FBC-2004424.2.6.6.3 (1,2,3) ENTRAP-
 MENT AVOIDANCE. (DETAIL)
 4) FBC-2004424.2.6.6.4 MINIMUM OF TWO
 SUCTION INLETS SHALL BE PROVIDED FOR EA
 PUMP. SEPARATED BY A MINIMUM OF 3 FEET
 OR LOCATED ON TWO DIFFERENT PLANES.
 (DETAIL)
 5) FBC-2004424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.(DETAIL)
 6) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 7) FBC-2004 424.2.9 WATER SUPPLY, LOCAL
 ORD.#2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
 8) FBC-2004 BLDG. 13-612.1.ABC.2.3.3
 TIME CLOCKS SHALL BE INSTALLED ON
 PRIVATE POOLS.
  