| 2005-12-30 00:00:00 | DENIED |
| | |
| | REFERENCE: FBC-2004 424.2 SWIMING POOLS |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING IN- |
| | FORMATION REQUIRED FOR PLAN REVIEW. |
| | 1) FBC-2004 SEC 424.2.6.6 ENTRAPMENT |
| | PROTECTION FOR SUCTION INLETS. (DETAIL) |
| | 2) FBC-2004424.2.6.6.2 SHOW COMPLIANCE |
| | WITH ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUF INFO FOR VAC LOCK. |
| | (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| | 3) FBC-2004424.2.6.6.3 (1,2,3) ENTRAP- |
| | MENT AVOIDANCE. (DETAIL) |
| | 4) FBC-2004424.2.6.6.4 MINIMUM OF TWO |
| | SUCTION INLETS SHALL BE PROVIDED FOR EA |
| | PUMP. SEPARATED BY A MINIMUM OF 3 FEET |
| | OR LOCATED ON TWO DIFFERENT PLANES. |
| | (DETAIL) |
| | 5) FBC-2004424.2.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER.(DETAIL) |
| | 6) FBC-2004 424.2.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. (DETAIL) |
| | 7) FBC-2004 424.2.9 WATER SUPPLY, LOCAL |
| | ORD.#2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | 8) FBC-2004 BLDG. 13-612.1.ABC.2.3.3 |
| | TIME CLOCKS SHALL BE INSTALLED ON |
| | PRIVATE POOLS. |
| | |