| Plan Review Notes For Permit 05120265 |
| Permit Number |
05120265 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-12-28 00:00:00 | ********* UNSAT ********* | | | | | | 1)NOTE: PLEASE CORRELATE ELECTRICAL | | | DETAIL ON PLANS WITH THE 8 1/2X 11 | | | SUBMITTED BY EASTERN EELCTRIC WHICH | | | MENTIONS NEW PANEL ETC. | | | PLEASE SEETHIS SAME SHEET MENTIONS A | | | 30A SERVICE TO POOL PANEL AND ALSO | | | MENTIONS, POOL PANEL AS 80A? | | | PLEASE SEE DETAIL ONENGINEER'S PLANS | | | DOES NOT INCLUDE THE SAME INFORMATION.? | | | | | | 2)NOTE: PLEASE SEE THE PLANS REFERENCE | | | THE 2005 NEC?, PLEASE KNOW, THE STATE | | | HAS NOT YET ADOPTED THE 2005 CODE. | | | (PROBABLY NOT UNTIL OCT 2006 AT THE | | | EARLIEST). | | | | | | 3)NOTE: | | | | | | 4)NOTE: PLEASE INCLUDE MIN LOAD | | | CALCULATIONS FOR ADDED LOADS. | | | PLEASE INCLUDE CONTINUOUS LOADS AT 125%. | | | PLEASE INCLUDE SIZE OF EXISTING SERVICE. | | | 215.3,230.42, 220 ETC. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE IN CONTACTING | | | THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW. | | | 561-805-6717 | | | [email protected] |
|