| 2007-11-01 08:52:17 | |
| | ** DENIED REVISION** |
| | |
| | |
| | 1) NOTE: PLEASE CLARIFY WHERE REVISION #8 IS LOCATED AS |
| | LISTED ON REVISION TITLE BLOCK. |
| | FBC 106.1.2 FOR COORDINATION AND ADDITIONAL |
| | INFORMATION. |
| | |
| | 2) NOTE: PLEASE SEE RECEPTACLE ALONG KITCHEN WALL |
| | WITHIN 6FT OF DOOR IS STILL MISSING PER 210.52. |
| | REDLINED ON PREVIOUS PLANS. |
| | |
| | 3) NOTE: PLEASE SEE KITCHEN WALL RECEPTACLES STILL |
| | SHOWN ON LIVING ROOM CIRCUIT WHICH IS NOT PERMITTED PER |
| | 210.52B1. |
| | |
| | 4) NOTE: PLEASE SEE BATHS 1 AND 2 ARE BOTH SHOWN |
| | CIRCUITED TOGETHER WHICH IS NOT PERMITTED PER 210.11C3. |
| | MAY ONLY CIRCUIT THE RECEPTACLES TOGETHER OR IF |
| | LIGHTING ETC IS ON WITH THE RECEPTACLE THEN NO OTHER |
| | AREAS OR ELECTRICAL IS PERMITTED TO BE FED. MAY NOT |
| | CIRCUIT AS SHOWN. |
| | |
| | 5) NOTE: PLEASE SEE SHEET A-2 AS THIS SHOWS PANEL AS |
| | 150AMPS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |