| 2007-04-05 13:26:59 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE SEE RISER DIAGRAM AND PLANS DO NOT |
| | MATCH. PLEASE SEE THAT THE PANEL *B* STILL DOES NOT |
| | INCLUDE ANY BREAKER OR OCP FEEDING PANEL *A*.. |
| | 215.5, 240.4, 310.16 |
| | |
| | 2) NOTE: PLEASE SEE THAT NEW SMOKE ALARM CIRCUIT |
| | REQUIRES ARC FAULT PROTECTION PER 210.12. |
| | PLEASE SEE THAT ALL CIRCUITS IN SLEEPING ROOMS FOR LTS, |
| | SA?S , RECEPTS AND FANS ARE AFCI. |
| | |
| | 3) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU?S #1 |
| | AND #2. |
| | 440.11 |
| | |
| | 3) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL BOTH SEEM |
| | TO SHOWN TO THE SAME DEVICE/YOKE. PLEASE SEE 210.4 AS |
| | IF THIS IS INDEED AS SHOWN THEN THIS WOULD REQUIRE THE |
| | BOTH OF THESE ON A 2-POLE BREAKER. |
| | |
| | 4) NOTE: PLEASE SEE JACUZZI TUB, PLEASE VERIFY THE |
| | BREAKER AND CONDUCTOR SIZE. THE SIZE OF THE CONDUCTORS |
| | WAS CHANGED TO #12 AWG, YET THE BREAKER WAS LEFT AT |
| | 15AMPS? |
| | PLEASE VERIFY THIS AS IT IS NOT A CODE VIOLATION ONLY A |
| | COMMENT. |
| | |
| | 5) NOTE: PLEASE SEE THAT NO HAND-DRAWN CHANGES ARE TO |
| | BE MADE TO PLANS. PLEASE SEE SEVERAL AREAS WHICH |
| | HAND-WRITTEN ITEMS WERE CHANGED. |
| | PLEASE REVISE THESE WHEN MAKING CORRECTIONS TO OTHER |
| | COMMENTS. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE PLANS ARE NOW CALLING FOR THE |
| | CODES TO BE LISTED UNDER THE 2005 NEC WHEN IN FACT THIS |
| | PROJECT WAS PERMITTED UNDER THE 2002 NEC. |
| | PLEASE LIST THE FOLLOWING CODES. |
| | 2002 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 7) NOTE: PLEASE SEE RECEPTACLES IN KITCHEN, DINING, |
| | BREAKFAST AREAS ARE TO BE ON ONE OR MORE OF THE SMALL |
| | APPLIANCE CIRCUITS. PLEASE SEE 210.52B1, 210.11C1, |
| | 220.16. |
| | PLEASE SEE SOME SHOWN ON THE LIGHTING CIRCUITS, THIS IS |
| | NOT PERMITTED. |
| | |
| | 8) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE |
| | COMPLETE WITH ALL CIRCUITS TO ROOMS AND AREAS IN WHICH |
| | THEY FEED. THE USE OF *GENERAL LIGHTING * OR GEN |
| | RECEPTS* IS NOT PERMITTED. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE CODE IN 408.4 |
| | * |
| | CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |