| Date |
Text |
| 2005-12-29 00:00:00 | ************ UNSAT ************ |
| | |
| | *** PLEASE SEE SOME OF THE SAME NOTES |
| | ARE FOR THE REVIEWS DONE UNDER OLD |
| | "REMODEL" PERMIT OF 04120970. |
| | |
| | ** PLEASE SEE A 4X FEE WAS ADDED AS PER |
| | "HOLD" WHICH WAS IN COMPUTER AT TIME OF |
| | APPLICATION, HOWEVER WAS NOT ASSESSED. |
| | PLEASE KNOW THIS PROPERTY HAD A |
| | "STOPWORK" ORDER GIVEN IN 2003 FOR THE |
| | REAR ADDITION WHICH IS IN FULL EFFECT. |
| | FEES OWED. |
| | |
| | *************************************** |
| | PLEASE SEE NUMEROUS LOCATIONS ON PLANS |
| | IN WHICH PLANS ARE REFERENCING THE 2001 |
| | FBC, PLEASE KNOW THE FBC IS NOW THE 2004 |
| | EDITION WHICH WENT INTO EFFECT ON OCT. |
| | 1ST, 2005 |
| | |
| | 1)NOTE: PLEASE SEE PLANS STILL DO NOT |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON TAKING RESPONSIBILITY OF |
| | SAID PLANS /DESIGN. |
| | PLEASE SEE FBC ADMINISTRATIVE SECTION, |
| | 106.3.4.3 |
| | |
| | 2)NOTE: PLEASE CLARIFY SERVICE ONCE |
| | AGAIN, PLEASE SEE SERVICE EQUIPMENT OF |
| | SOME SORT IS BEING SHOWN AS 250A'S? BUT |
| | IS UNCLEAR IF THIS IS METER/MAIN OR A |
| | 250A MB PANEL WITH SUB BRANCH BRKRS? NO |
| | SCHEDULE SUBMITTED? |
| | PLEASE INDICATE THE SIZE OF THE NEW |
| | METERCAN(ASBUILT). |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE #14 AWG STILL BEING |
| | SHOWN WITH 20A OCP. |
| | 240.4, 310.16 |
| | |
| | 4)NOTE: PLEASE SEE MISSING SD'S AS |
| | REQUIRED UNDER 2002 NFPA-72 11.5.1.1 |
| | SD'S INSIDE AND OUTSIDEALL SLEEPING |
| | RMS. SEE 2ND FLR. |
| | |
| | 5)NOTE: PLEASE SEE MISSING RECEPT W/IN |
| | 6' OF DOOR WAY. 210.52 |
| | |
| | 6)NOTE: PLEASE SEE PLANS ARE STILL |
| | SHOWING THE AHU OUTSIDE??? |
| | PLEASE SHOW ALL A/C EQUIPMENT ON PLANS |
| | ALONG WITH THE REQUIRED DISCONNECTS PER |
| | 440.11 |
| | |
| | 7)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B)ATTACHED. PLEASE SEE IS |
| | PLANS COME BACK IN WITHOUT COMMENTS |
| | BEING FULLY ADDRESSED, PLANS SHALL BE |
| | TURNED INTO THE STATE FOR PEIR REVIEW BY |
| | THE FLORIDA BOARD OF ENGINEER'S. |
| | |
| | |
| | |
| | ** PLEASE SEE BLDG NOTES, AS PLANS SHOW |
| | DOORS AS BEING "FRENCH DOORS", HOWEVER |
| | SLIDING DOORS ARE INSTALLED. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2005-12-27 00:00:00 | IN ELEC FOR REVIEW, ON HOLD UNTIL4X |
| | FEE AS SHOWN IN COMPUTER IS CLEARED OR |
| | FEES ACCESSED. |
| | SHOULD HAVE BEEN ASSESSED WHEN SUBMITTED |
| | OR SIGNED OFF BY A BLDG DEPT MANG. |