| Plan Review Notes For Permit 05120211 |
| Permit Number |
05120211 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-01-03 00:00:00 | 1)ALLINFORMATION/DRAWINGS/SPECIFICATIONS | | | | | | AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPON- | | | SIBLE FOR THE DESIGN. SECTION 104.2.1 | | | | | | 2) 11-4.8.2 SLOPE & RISE. THE LEAST | | | POSSIBLE SLOPE SHALL BE USED FOR ANY | | | RAMP. THE MAXIMUM SLOPE FOR A RAMP IN | | | NEW CONSTRUCTION SHALL BE 1 TO 12. THE | | | MAXIMUM RISE FOR RUN SHALL BE 30" (SEE | | | FIGURE 16). | | | | | | 3) WPB AMENDMENTS 106.1.3 BUILDING PLANS | | | SHALL BE DRAWN TO A MINIMUM 1/8 INCH | | | SCALE. DRAWINGS SUBMITTED ARE NOT DRAWN | | | TO SCALE. PLEASE COMPLY..ALSO SEE | | | SEC. 106.1.2 | | | | | | 4) PLEASE INDICATE ON DRAWINGS WHAT IS | | | EXISTING AND WHAT IS NEW. ALSO THE | | | DIMENTIONS OF THE RAMP AND PLATFORM | | | INCLUDING HEIGHT/LENGTH/SLOPE AND WIDTH | | | IS REQUIRED. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | 805-6726 | | | | | | |
|